Installation and start-up of UPS B9000FXS
Installazione e avviamento B9000FXS
30
OMD10081 REV. I
Picture 8 – Auxiliary terminals of B9000FXS
4.4.1 External manual bypass
Auxiliary contact of the External Manual Bypass Switch on terminals MBY1-MBY2.
A normally open contact has to be connected to the UPS terminals (MBY1-MBY2); when the
contact is closed (see Manual Bypass procedure), the microprocessor will acquire the status of
the contact and shut down the inverter.
4.4.2 Diesel generator (DIESEL MODE)
Auxiliary contact of the Diesel Generator on terminal XD1-XD2.
A normally open contact has to be connected to XD1-XD2 terminals, when the contact is
closed (if diesel mode is enable) the microprocessor will acquire the status of the contact and
the rectifier will reduce the voltage to the value set.
4.4.3 Auxiliary battery contact
Aux battery contact on terminals BAC1-BAC2.
This auxiliary contact is necessary to indicate the position of the isolator (open-closed) and the
fuse status.
4.4.4 Remote emergency power off (EPO)
Aux EPO contact on terminals EAC1-EAC2.
The voltage supply to the loads can be interrupted from a remote location by using this contact
(i.e. for safety requirements). A normally closed contact must be connected to the UPS
terminals (EAC1-EAC2); when this contact is open the static inverter and by-pass switches are
opened so that the output supply is interrupted.
Summary of Contents for ASD10
Page 1: ...OPERATING MANUAL UPS MANUALE OPERATIVO UPS B9000FXS 60 80 100 125 160kVA ...
Page 2: ......
Page 5: ...Warnings and general information Avvertenze e informazioni generali 2 OMD10080 REV B ...
Page 96: ...UPS user manual Utilizzo dell UPS OMD10082 REV F 5 ENGLISH LANGUAGE ...
Page 142: ...UPS user manual Utilizzo dell UPS OMD10082 REV F 51 LINGUA ITALIANA ...