50
Input Type
Support dual input
Phase
single
Voltage Range
176-276Vac
Frequency Range
(45~55)/(54~66)Hz
Current
32A@230Vac
52A@230Vac
Power Factor
0,99 @100% Nominal Load
0,98 @50% Nominal Load
0,95 @25% Nominal Load
THDI
< 5 %@Full load and battery full charged
Battery & Charger
Voltage
180VDC
240VDC
Current
39A
48A
Charger current
>8A
>8A
7.2 Dimension and Weight
Model
B500-R060-C
B500-R100-C
Dimension
(W*D*H) mm
438*640(594)*129
438*640(594)*215.5
Net Weight (KG)
19.0
26.0
Gross Weight (KG)
22.8
30.8
7.3 Operating Environment
Item
B500-R060-C/
B500-R100-C
Standards/Comments
Cooling
Force Air Cooling
/
Operating
Temperature Range
0°C ~ 40 °C
Nominal power &
continuous operating mode
Storage
Temperature
-15°C~60°C
UPS
0~35°C
Battery
Relative Humidity
0-95%
No condensing
Altitude
<1000m for Nominal
Over 1000 m the power