18
Fig. 4-7 B500EVO-200-B Input and output Terminal Block and ground
screw wiring diagram
Important notes:
If the UPS is used in single mode, JP1 and JP2
must be connected. If the UPS is used in parallel mode, the Jumper
between JP1 and JP2 must be removed.
Use cable cross section and protective device specification
Model
B500EVO-100-B
B500EVO-200-B
Input L1,L2,L3
Min.conductor cross section[m
㎡
]
Max.conductor cross section[m
㎡
]
2.5
4
6
10
Input L1,L2,L3 breaker (A)
40A,250VAC
60A,250VAC
Input N, M2
Min.conductor cross section[m
㎡
]
Max.conductor cross section[m
㎡
]
10
13
21
25
Input M2 breaker (A)
63A,250VAC
100A,250VAC
Input fuse (A)
30A,250VAC
50A,690AC
Output L,N,
Min.conductor cross section[m
㎡
]
Max.conductor cross section[m
㎡
]
10
13
21
25
www.upsdirect.com