OMD10078 rev F
40
Cabinet
AS764 (50 blocks)
AS764 (100 blocks)
Weight without battery - kg
360 720
Cabinet
AS764 (50 blocks)
AS764 (100 blocks)
Number of 12V blocks
50 100
Max. dim. of single block (mm)
350x190x290
350x190x290
Max. nominal capacity per block
140 Ah
140 Ah
Weight of single block
45 kg
45 kg
4.11.1.2 Connections
The following picture shows the electrical connections between the UPS and the
external battery cabinets.
Picture 30 – Battery cabinets connections
The connection cables are two power cables, whose section is shown in the following
table and length ranging from 2 to 50m. Longer cables are subject to excessive voltage
drop, so their section must be increased accordingly.
UPS (kVA)
60 80 100
125
160
Battery cables (mm
2
)
2x50
2x70 2x95 2x120
2x150