OMD39088 rev F
32
4.4.4 Environmental installation conditions
The air is classified by the EN 60721-3-3 standard (Classification of environmental
parameters and their severities – Stationary use at weather-protected locations) based
on climatic and biological conditions as well as on mechanically and chemically active
substances.
Therefore the place of installation must meet specific requirements to ensure
compliance with the conditions for which the UPS was designed.
Climatic conditions according to the technical specification of B9600FXS
Environmental parameter
Minimum operating temperature (°C)
– 10
Maximum operating temperature (°C)
+ 40
Minimum relative humidity (%)
5
Maximum relative humidity (%)
95
Condensation
NO
Rainfall with wind (rain, snow, hail, etc.)
NO
Water with an origin other than rain
NO
Ice formation
NO
Classification of biological conditions (EN 60721-3-3)
Environmental
parameter
Class
3B1
3B2
3B3
a) Flora
NO
Presence of mildew, fungus,
etc.
Presence of mildew, fungus,
etc.
b) Fauna
NO
Presence of rodents and
other animals that are
harmful to products,
excluding termites
Presence of rodents and
other animals that are
harmful to products, including
termites
Classification of mechanically active substances (EN 60721-3-3)
Environmental parameter
Class
3S1
3S2
3S3
3S4
a) Sand [mg/m
3
]
No
30 300
3000
b) Dust (suspension) [mg/m
3
]
0,01 0,2 0,4 4,0
c) Dust (sedimentation) [mg/(m
2
·h)
0,4 1,5 15 40
Places where precautions have been taken to minimize the
presence of dust. Places away from dust sources
x
Places without any special precaution to minimize the
presence of sand or dust, however not in proximity to sand or
dust sources
x
Places in proximity to sand or dust sources
x
Places in proximity to working processes that generate sand
or dust, or in geographic areas having a high proportion of
sand brought by the wind or of dust suspended in the air
x
Summary of Contents for B9600FXS
Page 28: ...OMD39088 rev F 27 Picture 21 Handling of UPS B9600FXS 500 600kVA ...
Page 39: ...OMD39088 rev F 38 Picture 28 Terminal board B9600FXS 400kVA side view ...
Page 40: ...OMD39088 rev F 39 Picture 29 Terminal board B9600FXS 500 600 800kVA front view ...
Page 41: ...OMD39088 rev F 40 Picture 30 Terminal board B9600FXS 500 600 800kVA side view ...