OMX76014 Rev. A
4.4.6 DC Voltage Settings
The DC Voltage Settings menu allows you to set the output voltage of the rectifier.
Drop-down menu
Description
MAX VOLTAGE
(Maximum output
voltage)
Sets the threshold for alarm A5
(1)
.
MAX VOLT. DELAY
(Max voltage standby
time)
Sets standby time on alarm A5 activation
MIN VOLTAGE
(Minimum output voltage)
Sets the threshold for alarm A6.
EMERGENCY LEVEL
(Emergency level)
Sets the emergency level voltage value.
(1)
A5 is an alarm whose activation disables the rectifier bridge.
4.4.7 ModBus settings
There are two ModBus Setting menus which allow you to set the ModBus
communication parameters for port 1 and 2.
Drop-down menu
Description
Address
Sets the ModBus slave address (from 1 to 247)
Transmission speed
Sets the transmission speed of the data on the
communication serial port.
Mode
Sets the parity and number of bits for stoppage on
the communication serial port.
4.4.8 Clock settings
The Clock Settings allow you to set the date and time of the rectifier.
Figure 13
–
Settings Menu - Clock
Date and time are regulated correctly.
The correct date and time settings are fundamental to save the archive of the
events logs.
4.4.9 Language settings
This Language settings menu allows you to change the language of the menu
choosing from ENGLISH (U.K.) and ITALIAN.
Summary of Contents for E2001 COMPACT
Page 1: ...OPERATING AND MAINTENANCE MANUAL E2001 COMPACT E3001 COMPACT ...
Page 2: ......
Page 4: ......
Page 8: ...UPS general description installation 4 OMX76013 REV A ...
Page 18: ......
Page 22: ...Front panel AC UPS GD 128x64 4 OMX76014 Rev A ...
Page 58: ......
Page 60: ...Start up shut down manual bypass 2 OMX76015 REV A ...