INGENIO COMPACT
ИБП руководство пользователя
INGENIO COMPACT
UPS user manual
30
OMS90051 РЕД. / REV. A
3.2.2 Battery charger / Booster
A bi-directional DC/DC converter is placed between the batteria and the DC bus; the converter
has a double function.
When the mains is present and the rectifier operational the converter works as battery charger,
restoring the energy lost by the battery and keeping it in floating charge.
In case of mains or rectifier failure the battery supplies energy to the inverter through the
converter, which works as booster stage.
As the mains is back the rectifier provides energy to the inverter and the converter restores its
function as battery charger.
3.2.3 Inverter
It converts the direct voltage coming from the rectifier or from the DC battery into alternating AC
voltage stabilized in amplitude and frequency.
The fully digital control of the output sine-wave allows to achieve high performances, among
which a very low voltage distortion even in presence of high-distorting loads.
3.2.4 Battery
The battery can be installed inside or outside the UPS.
The battery is charged, according to the DIN 41773 Standard, every time it has been partially or
completely discharged. When its full capacity is restored, it is kept floating so as to compensate
for any self-discharge.
3.2.5 Static bypass
The Static Bypass allows to transfer the load between Inverter and Emergency Mains, and vice-
versa, in a very short time, and uses SCR’s as power commutation elements.
3.2.6 Manual bypass
The Manual Bypass is used to cut off the UPS completely, supplying the load directly from the
input mains in case of maintenance or serious failure.
Follow the procedures contained in the manual
The sequence of manual bypass switching and return must be carried out with
respect to the procedure indicated in the installation and start-up section. The
manufacturer cannot accept responsibility for damages arising from incorrect
operation.
Summary of Contents for INGENIO COMPACT
Page 2: ...РУКОВОДСТВО ПО ЭКСПЛУАТАЦИИ ИБП OPERATING MANUAL UPS INGENIO COMPACT 10 20 кВА ...
Page 6: ...Предупреждения и общие сведения Warnings and general information 2 OMB81277 РЕД A ...
Page 8: ...Предупреждения и общие сведения Warnings and general information 4 OMB81277 РЕД A ...
Page 14: ...Предупреждения и общие сведения Warnings and general information 10 OMB81277 РЕД A ...