Монтаж и пуск INGENIO COMPACT ИБП 10÷20 кВА
Installation and start-up of INGENIO COMPACT 10÷20 kVA
58
OMS90050 РЕД. / REV. A
Mains connection
The connection to the mains must be carried out with protection devices between the
mains and the UPS.
The use of differential protection devices in the line supplying the UPS is
unadvisable. The leakage current to ground due to the RFI filters is rather high and it
can cause spurious tripping of the protection device.
According to EN62040-1 standard, in order to take into account the UPS’ leakage
current, residual current devices having adjustable threshold can be used.
Mains connection
Include an appropriate and readily accessible disconnecting device in the
electrical line connecting the UPS to the mains.
4.1 CONNECTION OF THE POWER CABLES
For the electric connection of the INGENIO COMPACT UPS 10÷20 kVA, connect the following
cables:
DC supply from the battery (if the battery is external);
AC supply from the rectifier and bypass supply mains;
AC output to the loads.
Injury hazard due to electric shock!
Very high voltages are present at the ends of the cables coming from the battery:
Isolate the battery via DC circuit breakers before connecting it to the UPS;
Connect the ground cable to the relevant bar before carrying out any other
connection inside the device.
Risk of damages to the device due to insufficient insulation
The cables must be protected from short-circuits and leakage currents to earth;
the connection points must be hermetically sealed to prevent the air from being
sucked through the cable passage.
Risk of damages to the device due to incorrect wiring
To connect the device, follow the electrical drawing scrupulously and respect the
polarity of cables.
Summary of Contents for INGENIO COMPACT
Page 2: ...РУКОВОДСТВО ПО ЭКСПЛУАТАЦИИ ИБП OPERATING MANUAL UPS INGENIO COMPACT 10 20 кВА ...
Page 6: ...Предупреждения и общие сведения Warnings and general information 2 OMB81277 РЕД A ...
Page 8: ...Предупреждения и общие сведения Warnings and general information 4 OMB81277 РЕД A ...
Page 14: ...Предупреждения и общие сведения Warnings and general information 10 OMB81277 РЕД A ...