UPS user manual
36
OMH44150 REV. B
5.3.4 Resetting the history log
The history log can be reset by entering the HISTORY RESET section; the operation
requires a further confirmation.
Loss of data
The alarms history contains very important data to monitor the device behaviour over
time. We recommend to save the data before deleting it.
5.3.5 Setting the RS485 user interface parameters
The parameters regarding the communication via RS485 interface can be set in the
COMMUNICATION section.
Picture 33 – Communication main page
The three sections are almost identical, and allows, for each one of the available
communication ports, to set the typical parameters, that is the ModBus address, the
communication mode and the data transmission speed.
The Teleservice port is reserved to the interface with a dedicated converter for the integration
within the BORRI teleservice system; the other two ports are available for the user.
5.3.6 New centralized battery
The page NEW CENTR BATT is used in case battery circuit breaker BCB is not closed,
when requested, in the start-up phase. In this case the system will start considering the battery
completely discharged and activating the alarm “A10 – BATTERY FAULT”.
To set the battery autonomy to 100% it is necessary to access the section and confirm the
operation in the confirmation page.
In case of distributed battery configuration such section is disabled and can be found in the
Settings section of each power module.
Summary of Contents for UPSaver 1000 kVa
Page 2: ...UPS OPERATING MANUAL UPSaver 400 1600 kVA ...
Page 5: ......
Page 7: ...Warnings and general information 2 OMH44148 REV A ...
Page 13: ......
Page 20: ...UPSaver installation and start up OMH44149 REV C 7 ...
Page 33: ...UPSaver installation and start up 20 OMH44149 REV C Picture 6 Handling of the power module ...
Page 57: ...UPSaver installation and start up 44 OMH44149 REV C Picture 46 UPS cabinets upper fixing ...
Page 59: ...UPSaver installation and start up 46 OMH44149 REV C Picture 49 Power module cables terminals ...
Page 115: ...UPS user manual 6 OMH44150 REV B ...