UPS user manual
38
OMH44150 REV. B
5.3.8 Centralized battery test
The CENTR BATT TEST section allows to carry out a short discharge test of the battery. In
case the battery is not efficient, the alarm “A10 – Battery fault” is generated at the end of the
test.
Possible loss of supply
This test can affect the continuity of supply to the loads if the battery is not fully
charged.
5.3.9 Setting the display network parameters
The NETWORK CONFIGUR section allows to configure the parameters related to the LAN
network and to the system time synchronization server.
All the parameters that can be set in this section are related to the communication ports (LAN
and RS485) available on-board the touch screen.
Picture 36 – Touch screen network parameters setting
5.3.9.1 Setting the LAN parameters
The LAN network parameters which can be set are the following:
IP address
Network mask
Network gateway
Primary DNS server
Secondary DNS server
DHCP Enabling / Disabling