installation and start-up
OMH44149 REV. C
21
3.3 INFORMATION
FOR
THE INSTALLATION
The
UPSaver
UPS must be installed indoor, in a clean and dry room, preferably without dust
or humidity infiltrations. For the environmental conditions in the place of installation, in
compliance with the current legislation, please refer to the “Wall clearances and ventilation”
section.
Special environmental conditions
It is necessary to implement specific protective measures in case of unusual
environmental conditions:
harmful smoke, dust, abrasive dust;
humidity, vapour, salt air, bad weather or dripping;
explosive dust and gas mixture;
extreme temperature variations;
bad ventilation;
conductive or radiant heat from other sources;
fungus, insects, vermin.
The positioning and the mechanical and electrical installation of the various modules
(interconnections) which compose the
UPSaver
system is generally performed either by
manufacturer's engineers or specialized service centres who hold the specific instructions.
3.3.1
UPSaver
basic configuration
As outlined in the previous paragraphs, the
UPSaver
system is essentially composed by two
modular elements:
power module;
input/output (I/O) module.
The input/output module (
I/O
) is composed of a central section containing the connection
terminal boards, the sectioning devices and the centralized static switches, when provided. It is
furthermore provided of side distribution columns which contain the power modules' input/output
switches.
Combining the power modules with the proper I/O module allows to obtain several system
typologies for what concern the configuration of the battery and the static bypass switch.
CB
Centralized Battery
A single battery for the
UPSaver
UPS is provided; a single battery static switch is installed in
the I/O module.
DB
Distributed Battery
Each power module which compose the
UPSaver
UPS is provided with its own battery. The
connection of the various battery banks is carried out in the I/O module, but each power
module is provided with its own battery static switch.
CSB
Centralized Static Bypass switch
A single bypass static switch is provided, which is installed in the I/O module.
Summary of Contents for UPSaver 1000 kVa
Page 2: ...UPS OPERATING MANUAL UPSaver 400 1600 kVA ...
Page 5: ......
Page 7: ...Warnings and general information 2 OMH44148 REV A ...
Page 13: ......
Page 20: ...UPSaver installation and start up OMH44149 REV C 7 ...
Page 33: ...UPSaver installation and start up 20 OMH44149 REV C Picture 6 Handling of the power module ...
Page 57: ...UPSaver installation and start up 44 OMH44149 REV C Picture 46 UPS cabinets upper fixing ...
Page 59: ...UPSaver installation and start up 46 OMH44149 REV C Picture 49 Power module cables terminals ...
Page 115: ...UPS user manual 6 OMH44150 REV B ...