SAVE THESE INSTRUCTIONS
11
Chimney
DO NOT CONNECT THIS UNIT TO A CHIMNEY FLUE SERVING
ANOTHER APPLIANCE
This room heater must be connected to a 6” factory built UL 103 type HT chimney in the Standard for
Chimneys, Factor-Built, Residential Type and Building Heating Appliance, UL 103 or a code-approved
masonry chimney with a flue liner.
Height of Chimney
A masonry chimney or a listed factory-build chimney must be the required height above the roof and
any other nearby obstructions such as trees buildings etc. The chimney must be at least 3’ (90 cm)
higher than the highest point where it passes through the roof and at least 2’ (60 cm) higher than the
highest part of the roof or structure that is within 10’ (305 cm) of the chimney, measured horizontally.