Vertically With New Chimney System
( Refer to fig. Nº 7a-7b)
fig. Nº7b
4 FT.
Vertically Into Existing Chimney System
( Refer to fig. Nº 8a-8b)
fig. Nº7a
24" MIN
ATTIC
INSULATION
SHIELD
CEILING
SUPPORT/
FIRESTOP
SPACER
PIPE
ADAPTER
TEE WITH
CLEAN-OUT
ADAPTER
24" MIN
NOTE:
Follow L-Vent chimney manufacturer’s instructions.
OPTION:
Install L-Vent elbow in place of clean-out tee. Locate stove. Drop plumb bob to center of tee outlet, mark point on ceiling. Install
ceiling support and L-Vent pipe per L-Vent manufacturer’s instructions.
•
Always maintain 3” clearance from combustible materials. When passing through additional floors or ceilings, always install firestop
spacer.
•
After lining up for hole in roof, cut either around or square hole in roof, always 3” larger all the way around pipe. Install upper edge
and sides of flashing under roofing materials, nail to the roof along upper edge. Do not nail lower edge. Seal nail head with non-
hardening waterproof mastic.
•
Apply non-hardening, waterproof mastic where the storm collar will meet the vent and flashing. Slide storm collar down until it
sits on the flashing. Seal and install cap. Mobile home installations must use a spark arrester.
Adapters are available to adapt from 3” L-Vent to 6” or 8” Class-A chimney. (Fig. Nº 8a)
As an alternative, 3” or 4” L-Vent can be run inside existing chimney to termination. (Fig. Nº 8b). This is the preferred method.
Follow guidelines for equivalent.
OWNER´S MANUAL
-10-
FIRESTOP