Technical information
21
Compress 7000i AW – 6721830633 (2021/02)
Table 7 Specifications – heat pump (alternating current)
Table 8 Detailed sound pressure level, heat pump (alternating current)
Table 9 Detailed sound pressure level of heat pump incl. acoustic covers at front and back (accessories)
Table 10 Detailed sound pressure level, heat pump (alternating current)
Table 11 Detailed sound pressure level of heat pump (alternating current) acoustic covers at front and back (accessories)
Table 12 Detailed sound pressure level, heat pump (alternating current)
3) Sound power level in accordance with EN 12102
4) GWP100 = 2088
Detailed sound pressure level (max.) 5 OR-S
Clearance
m
1
2
3
4
5
6
8
10
12
14
16
Day
>3 m
1)
1) Heat pump more than 3 m from the wall
dB (A)
53
47
43
41
39
37
35
33
31
30
29
<3 m
2)
2) Heat pump closer than 3 m to the wall
dB (A)
56
50
46
44
42
40
38
36
34
33
32
Night
>3 m
dB (A)
47
41
37
35
33
31
29
27
25
24
23
<3 m
dB (A)
50
44
40
38
36
34
32
30
28
27
26
Detailed sound pressure level (max.) 5 OR-S incl. acoustic covers at front and back (accessories)
Clearance
m
1
2
3
4
5
6
8
10
12
14
16
Day
>3 m
1)
1) Heat pump more than 3 m from the wall
dB (A)
50
44
40
38
36
34
32
30
28
27
26
<3 m
2)
2) Heat pump closer than 3 m to the wall
dB (A)
53
47
43
41
39
37
35
33
31
30
29
Night
>3 m
dB (A)
43
37
33
31
29
27
25
23
21
20
19
<3 m
dB (A)
46
40
36
34
32
30
28
26
24
23
22
Detailed sound pressure level (max.) 7 OR-S
Clearance
m
1
2
3
4
5
6
8
10
12
14
16
Day
>3 m
1)
1) Heat pump more than 3 m from the wall
dB (A)
55
49
45
43
41
39
37
35
33
32
31
<3 m
2)
2) Heat pump closer than 3 m to the wall
dB (A)
58
52
48
46
44
42
40
38
36
35
34
Night
>3 m
dB (A)
50
44
40
38
36
34
32
30
28
27
26
<3 m
dB (A)
53
47
43
41
39
37
35
33
31
30
29
Detailed sound pressure level (max.) 7 OR-S incl. acoustic covers at front and back (accessories)
Clearance
m
1
2
3
4
5
6
8
10
12
14
16
Day
>3 m
1)
1) Heat pump more than 3 m from the wall
dB (A)
50
44
40
38
36
34
32
30
28
27
26
<3 m
2)
2) Heat pump closer than 3 m to the wall
dB (A)
53
47
43
41
39
37
35
33
31
30
29
Night
>3 m
dB (A)
46
40
36
34
32
30
28
26
24
23
22
<3 m
dB (A)
49
43
39
37
35
33
31
29
27
26
25
Detailed sound pressure level (max.) 9 OR-S
Clearance
m
1
2
3
4
5
6
8
10
12
14
16
Day
>3 m
1)
1) Heat pump more than 3 m from the wall
dB (A)
56
50
46
44
42
40
38
36
34
33
32
<3 m
2)
2) Heat pump closer than 3 m to the wall
dB (A)
59
53
49
47
45
43
41
39
37
36
35
Night
>3 m
dB (A)
50
44
40
38
36
34
32
30
28
27
26
<3 m
dB (A)
53
47
43
41
39
37
35
33
31
30
29
Detailed sound pressure level (max.) 9 OR-S incl. acoustic covers at front and back (accessories)
Clearance
m
1
2
3
4
5
6
8
10
12
14
16