Installation & Operation Manual
Bosch Inverter Ducted Packaged Heat Pump
| 21
BTC 761701105 A | 03.2019
Data subject to change
Figure 26
Ensure the temperature sampling position as shown above.
If calculated subcooling value is lower than the design
subcooling value (Table 12), please add refrigerant. Repeat
steps 2 through 4.
Liquid
Line Temp
(°F)
Final Subcooling(°F)
6
7
8
9
10
11
12
13
Liquid Gauge Pressure (PSI)
55
173
176
179
182
185
188
191
195
60
188
191
195
198
201
204
208
211
65
204
208
211
215
218
221
225
229
70
221
225
229
232
236
239
243
247
75
239
243
247
251
255
259
262
266
80
259
262
266
270
275
279
283
287
85
279
283
287
291
295
300
304
309
90
300
304
309
313
318
322
327
331
95
322
327
331
336
341
346
351
355
100
346
351
355
360
365
370
376
381
105
370
376
381
386
391
397
402
407
110
397
402
407
413
418
424
430
435
115
424
430
435
441
447
453
459
465
120
453
459
465
471
477
483
489
496
125
483
489
469
502
508
515
521
528
Table 11
R-410A Refrigerant Chart - Final Subcooling
Heat Pump Model
Design Subcooling
BRB-60HWD1N1-M19
12°F ± 4°F
Table 12
5.
Adjust refrigerant level to attain proper gauge pressure.
Add refrigerant
if the subcooling reading from Table 11 is
lower than the designed value (Table 12).
Connect gauges to refrigerant bottle and unit as illustrated
(Figure 25).
Purge all hoses.
Open tank.
Stop adding refrigerant when subcooling matches the
charging chart (Table 11) Final Subcooling value.
Recover refrigerant
if the subcooling reading from Table 11 is
higher than the designed value (Table 12).
Figure 27
6.
Stabilize the system.
Wait 5 minutes for the system condition to stabilize
between adjustments.
When the subcooling matches the chart, the system is properly
charged.
Remove gauges.
Replace service port caps to prevent leaks. Tighten finger
tight plus an additional 1/6 turn.
7.
Record System Information for reference (Table12). Record system
pressures and temperatures after charging is complete.
The subcooling also can be calculated by pressing check button
after getting T3 and T3L temperatures (refer to table 17).
Description
Value
Outdoor model number
Measured Outdoor Ambient
°F
Measured Indoor Ambient
°F
Check Condenser Outlet Temp.(T3L)
°F
Check Condenser Temp.(T3)
°F
Calculate subcooling value =T3 ‒T3L
°F
Table 13