Installation & Operation Manual
Bosch Inverter Ducted Packaged Heat Pump
| 25
BTC 761701105 A | 03.2019
Data subject to change
13.7 Fault Code Table
Code
Fault Description (Sensor)
C3
The coil sensor is seated fault in cooling (T3)
E4
Temperature sensor fault (T3, T4, T5, Th, T3L, TF)
E5
High/low voltage protection
E6
DC fan motor fault
E7
Compressor discharge sensor is seated fault (T5)
E9
EEPROM fault
H0
Communication fault in main control chip
H5*
5 times (P2) protection in 100 minutes, system lockout
H8
Pressure transducer fault (PT)
P0
High module radiator temperature protection (TF)
P1
High pressure switch protection (HPS)
P2
Low pressure protection in cooling or heating (PT)
P3
Compressor over current protection
P4
High compressor discharge temperature protection (T5)
P5
Condensor coil temperature protection in cooling (T3)
P8
DC fan motor hurricane/typhoon protection
PH
Low discharge superheat protection
F1
High pressure switch protection (HPS)
L0-L9
The IPM module protection
AtL
Ambient Temperature Limited
System Protection Status Codes**
Forced operation mode
L
Running indication under T3 limited condition
D
Running indication under T5 limited condition
P
Running indication under compressor ratio limited condition
F
Running indication under TF limited condition
C
Running indication under current limited condition
U
Running indication under low voltage limited condition
A
Running indication under return oil mode
dF
Running indication under defrost mode
Table 16
* Fault requires hard restart
** If the fi rst digit shown on the control board LED is one of the following protection
codes (followed by two numerical digits which show the current compressor frequency in Hz), the unit will continue to run but in a limited condition. The
only exception is when the system is in defrost mode, which only displays "dF" (without any numerical digits following).