13.8 Parameter Point Check Table
To display system parameters, press the “Check” button to index
through the series of parameters available. The first time you
press the “Check” button, it will display the sequence, and after
1 second it will display the value of the parameter. If you press
the “Check” button again, it will display the next sequence. Refer
to Figure 30 for check button location on the control board.
Normal Status, last two digits will display under the following
conditions
i. Unit not operating (Standby Mode); “outdoor ambient
temperature”.
ii. Unit operating; displays “compressor operating frequency”.
After 20 seconds on same parameter, the display will revert back
to normal status.
If a system protection is active, first digit will display “status
code”.
No.
Point check content
Example
Remark
0
Outdoor unit capacity
H5
H5=Heat Pump 5 ton
1
Outdoor unit mode
2
0 standby,
2 cooling,
3 heating
2
Outdoor unit set compressor speed (Hz)
66
3
T3 (outdoor coil temp.) (°F)
4
T4 (outdoor ambient temp.) (°F)
5
T5 (compressor discharge temp.) (°F)
6
Th (compressor suction temp.) (°F)
7
T3L (condenser outlet temp.) (°F)
8
Tf (module temp.) (°F)
9
Pe (evaporating pressure) (PSI)
Low Suction Pressure
10
Pc (condensing pressure) (PSI)
High Head Pressure
11
Tes target of the evaporating temp. (only use for cooling mode) (°F)
12
Te (evaporating temp.) (°F)
13
Tcs target of the condensing temp. (only use for heatling mode) (°F)
14
Tc (condensing temp.) (°F)
15
Target of the compressor discharge superheat (only use for heating mode) (°F)
16
Compressor discharge superheat (°F)
17
Openings of EEV
18
Fan speed
19
Compressor current (A)
20
Power AC voltage Input (V)
21
Compressor input dc voltage (V)
22
Continuous running time of the compressor (min)
23
Last fault code
00
see Table 16
24
Software version
01
25
Remark“--”
--
--
Table 17