1 2 |
Bosch 3H/2C Touch-Technology Thermostat
Installation, Operation & Application Manual
08.2016
|
Bosch Thermotechnology Corp.
Data subject to change
Room Temperature Offset
(+9°F to -9°F) (+4.5°C to -4.5°C)
—
Adjust to calibrate displayed room temperature to match actual room
temperature.
—
Press the
or
to select. Press
to advance to the next
screen.
CONFIG
Figure 19
Maximum Cycles Allowed Per Hour
(- -, 2-6)
—
= as many as needed, 2-6 = maximum cycles/hour
—
Press the
or
to select. Press
to advance to the next
screen.
CONFIG
Figure 20
Fan Delay Off Time
(0, 30, 60, 90 seconds)
—
Select the amount of time the fan continues to operate after the cool/
heat demand has been satisfied. Functions for cooling, heat pumps
and electric heat.
—
Press
or
to select.
—
Press
to advance to the next screen.
CONFIG
Figure 21
Hourly Cycle Fan Operation
(1-30 minutes per hour)
—
Used in conjunction with the Fan HOURLY mode. When the user
selects this option, the fan will turn on at the beginning of every hour
and run for the number of minutes indicated here.
—
Press
or
to select.
—
Press
to advance to the next screen.
CONFIG
HOURLY
Figure 22
Fan on Schedule
(OFF, WAKE, LEAVE, RETURN, SLEEP)
—
The fan will run continuously during this scheduled period when the
mode is not set to OFF. To turn on the fan during one of the scheduled
periods (WAKE, LEAVE, RETURN, SLEEP), please do the following:
—
Press
or
to select.
—
Press
to advance to the next screen.
CONFIG
ON
SCHEDULE
FAN
OFF
Figure 23
Check Filter Timer
(800-2500 hours)
—
After the number of (fan running) hours specified, (for example,
1200 hours), the words “CHECK FILTER” will display to remind you
to check/change the system filter. The next configuration screen is
where the elapsed number of run hours can be reset.
—
Press
or
to select.
—
Press
to advance to the next screen.
CONFIG
Check
Filter
Figure 24