Installation, Operation & Application Manual
Bosch 3H/2C Touch-TechnologyThermostat
| 7
Bosch Thermotechnology Corp.
|
08.2016
Data subject to change
4 Wiring diagram
T
H
E
R
M
O
S
T
A
T
A
RH
RC
C
Y1
W1
O/B
G
W2
Y2
UPM
Transformer
120 VAC
Fan
Heat #2
24 VAC
AUX
Heat #3
Cool/Compressor #1
Cool/Compressor #2
Heat #1/Reversing Valve
OUT
COM
ALR
Figure 2
Factory installed jumper between RH and RC is required.
Thermostat is powered between RH & C.
4.1 Terminal designator descriptions
A
– Alarm/display (24 VACinput, switched from RH)
RC, RH
– 24 VAC hot
C
– 24 VAC common
Y1
– 1st stage cool, 1st stage heat for heat pumps
Y2
– 2nd stage cool for 2-stage or 2-compressor systems. 2nd stage heat
for 2-stage or 2-compressor heat pump systems.
G
– Fan
W1/O/B
– Configurable
—
W1
– 1st stage heat for non-heat pump systems
—
O
– Cool active reversing valve
—
B
– Heat active reversing valve
W2
– 2nd stage heat for 1 compressor heat pump and non-heat pump
AUX
– 3rd stage heat