Regulations
Observe the following guidelines and standards:
• Local regulations
•
EnEG (Building Regulations)
(in Germany)
•
EnEV
(in Germany)
Installation of, and equipment for, heating and water heating systems:
•
DIN
and
EN
standards
–
DIN 4753-1
– Water heaters ...; requirements, identification,
equipment and testing
–
DIN 4753-3
– Water heaters ...; corrosion protection on the
water side with glass lining; requirements and testing
(product standard)
–
DIN 4753-7
– Water heaters, containers with a volume up to
1000 l, manufacturing, thermal insulation and corrosion
protection requirements
–
DIN EN 12897
– Water supply - regulation for ... DHW cylinders
(product standard)
–
DIN 1988-100
– Technical rules for potable water installations
–
DIN EN 1717
– Protection of potable water against pollution ...
–
DIN EN 806-5
– Technical rules for potable water installations
–
DIN 4708
– Central water heating systems
•
DVGW
– Code of Practise W 551 – Potable water heating systems and
pipework; technical measures to inhibit the growth of legionella
bacteria in new systems; ...
– Code of Practise W 553 – Sizing DHW circulation systems ...
Product data for energy consumption
•
EU Regulation
and
Directives
–
EU Regulation 2017/1369
–
EU Regulation 811/2013
and
812/2013
4
Transport
WARNING
Risk of injury from carrying heavy loads and inadequately securing
loads for transport!
▶ Use suitable means of transport.
▶ Secure the cylinder to prevent it falling.
▶ Move packed cylinder with a sack truck and lashing strap
(
Fig. 5, page 59).
-or-
▶ Move unpacked cylinder with a transport net, during handling,
protect connections against possible damage.
5
Mounting method
5.1
Installation location
NOTICE
Risk of damage from inadequate load-bearing capacity of the
installation surface or unsuitable floor surface!
▶ Ensure that the installation surface is level and offers sufficient load-
bearing capacity.
▶ Install the cylinder in a dry frost-free interior.
▶ If there is any danger of water accumulating on the floor of the
installation location: place the cylinder on a plinth.
▶ Observe the minimum wall clearances inside the installation room
(
Fig. 6, page 59).
▶ Align the cylinder vertically with the adjustable feet.
5.2
Installation
Preventing heat loss through natural circulation:
▶ Install non-return valves in all cylinder circuits.
-or-
▶ Connect pipework directly to the cylinder connections so that natural
circulation is prevented.
▶ Install connecting pipework free of stress.
5.2.1
Circulation
Connecting a DHW circulation line:
▶ Install a DHW circulation pump which is approved for potable water
and a non-return valve.
A DHW circulation line is not connected:
▶ Seal and insulate connection.
Circulation is only permitted with reference to the heat losses
during cooling with a time- and/or temperature-dependent DHW
circulation pump.
Size the DHW circulation line in accordance with DVGW Code of Practice
W 553. Observe special requirement according to DVGW W 511:
• Maximum temperature drop 5 K
To easily maintain the maximum temperature drop:
▶ Install a control valve with thermometer.
5.2.2
Connection on the heat source side
▶ Connect the flow at the top and the return at the bottom to the heat
exchanger.
▶ Keep primary lines as short as possible and insulate well. This
prevents unnecessary pressure losses and cooling down of the
cylinder due to water circulating through the pipework or similar.
▶ Provide effective ventilation (e.g. bleeding device) at the highest
point between the cylinder and wall mounted boiler to prevent faults
due to air locks.
▶ Install drain valve in the primary line.
It must be possible to drain the heat exchanger via this line.
Summary of Contents for 8735100975
Page 57: ...57 Stora 6721835341 2021 04 2 0010037827 001 1 1 13 2 3 4 9 10 11 13 14 12 8 5 6 7 ...
Page 59: ...59 Stora 6721835341 2021 04 4 1 WP 400 PK 2 WP 500 P 0010037816 001 5 6 ...
Page 60: ...Stora 6721835341 2021 04 60 7 8 ...
Page 61: ......
Page 62: ......
Page 63: ......
Page 64: ...Bosch Thermotechnik GmbH Junkersstrasse 20 24 D 73249 Wernau www bosch thermotechnology com ...