Access Easy Controller
Card Reader Keypad Functions | en
167
Bosch Security Systems
Hardware Manual
Ver 2.0.0 | 2006.07
LED turns to red light.
Buzzer will beep at a fast rate for 15 seconds.
The Alarm Zone is ARMED.
In the View Activity web page, you should see the Armed transaction as carried out by the par-
ticular card number, user name, time, date and location of reader. The status of the Input
Points is also shown on the Input Control web page.
Example 2 - Input Point #1 is in Normal State, while Input Point #2 is in the Open state.
1.
LED is flashing (Green/Red) in medium rate; indicating one of the input is in open state.
2.
Press 0 and present the arming card to Reader #4, to arm the Alarm zone.
LED is flashing (Green/Red) in slow rate
Buzzer will beep at a fast rate for 15 seconds.
The Alarm Zone is ARMED with Input Point #2 "bypassed".
In the View Activity web page, beside seeing similar transaction to Example 1, there will be a
Bypassed transaction for Input Point #2. The "bypassed" status for Input Point #2 is also
shown in the Input Control web page.
Example 3 : Alarm zone 1 is armed.
1.
LED is has a stable red light.
2.
When any one input is activated, the buzzer will beep in a low rate continuously.
3.
Present the disarming card to the reader.
Buzzer stop.
LED turns to green light
The Alarm Zone is DISARMED.
Disarming an Alarm Zone
To disarm an Alarm Zone, just present the arming card to the Reader.