background image

16

en | Connections

AMC2 enclosure with 1

DIN rail

2020-07 | V04 | F.01U.330.018

Bosch Security Systems B.V.

3.3.1

12 V mode operation

Notice!

Make sure that the power supply has the correct output voltage
(12 V).

+

-

B12

B7a

B8a

B7b

B8b

+

-

+

-

B12

B7a

B7b

B8a

B8b

Figure 3.3: 

12 V mode with one battery (left); 12 V mode with two batteries

(right)

12 V mode operation using one battery

1.

Set the switch of the power supply unit to 12 V.

2.

Connect B12 to the power supply interface labeled BAT.

3.

Connect B7b (black) to the rechargeable negative (-)
terminal of the battery.

4.

Connect B7a (red) to the rechargeable positive (+) terminal
of the battery.

5.

Attach the bracket to the back of the housing next to the
batteries.

6.

Attach the connectors B8a and B8b to the bracket

.

Summary of Contents for AEC-AMC2-UL01

Page 1: ...AMC2 enclosure with 1 DIN rail AEC AMC2 UL01 en Installation manual ...

Page 2: ......

Page 3: ...onents of the enclosure 4 1 2 Parts included 6 1 3 Cables to be assembled 8 2 Mounting the enclosure 10 3 Connections 11 3 1 Connecting the devices 11 3 2 Connecting the cables 13 3 3 Connections for supporting Universal Power Supply 15 3 3 1 12 V mode operation 16 3 3 2 24 V mode operation 18 4 Appendices 20 4 1 UL requirements 20 4 2 Cable assembly 21 ...

Page 4: ... 7 8 11 12 13 9 5 10 Figure 1 1 Components of the enclosure Position Description 1 Cover grounding point 2 Mounting rail for power supply unit PSU and Access Modular Controller AMC2 3 AMC2 grounding point 4 Cable knock outs for reader and signal cables 5 Temperature sensor bracket 6 Tamper contact 7 Fixing bracket for rechargeable batteries 8 Main grounding point ...

Page 5: ...ith 1 DIN rail System overview en 5 Bosch Security Systems B V 2020 07 V04 F 01U 330 018 Position Description 9 Label 10 Knock out for the power cable connection 11 Three pin connector 12 Bracket for LED 13 Name plate ...

Page 6: ...6 en System overview AMC2 enclosure with 1 DIN rail 2020 07 V04 F 01U 330 018 Bosch Security Systems B V 1 2 Parts included x3 x1 x1 x1 x2 A B E C D x1 F ...

Page 7: ...overview en 7 Bosch Security Systems B V 2020 07 V04 F 01U 330 018 Position Description A Cable ties to secure cables B Three screw anchors S8 and M6 50 screws C Bracket for cable fixing D Fuse and fuse holder E LED F Cover grounding cable ...

Page 8: ... with 1 DIN rail 2020 07 V04 F 01U 330 018 Bosch Security Systems B V 1 3 Cables to be assembled D A C B E F Position Description A Power supply cable AMC2 B Power supply cable battery C Battery cable D Cover contact wired E Power cable ...

Page 9: ...AMC2 enclosure with 1 DIN rail System overview en 9 Bosch Security Systems B V 2020 07 V04 F 01U 330 018 Position Description F Power cable with LED indicator UL required Refer to Cable assembly page 21 ...

Page 10: ...closure aside 5 Drill the holes at the points that you previously marked on the wall 6 Insert the screw anchors in the drilled holes 7 Drive the screws halfway into the top and bottom left screw anchors 8 Hang the enclosure on the wall according to the position of the screw anchors 9 Drive the third screw into the anchor on the bottom right 10 Tighten all screws The enclosure is installed 86 5 mm ...

Page 11: ...C N G L1 BAT RTH Power Supply AMC2 DC RS 485 EXT T OK L N C DC BAT AC 1 2 3 4 5 6 7 1 2 3 4 5 6 1 2 2 1 Figure 3 1 Connections in the enclosure 1 Insert the cables of the device through the knock outs at the top right side wall of the enclosure or through the rear of the enclosure 2 Provide an appropriate disconnect device to the supply line Warning Risk of electric shock Disconnect the mains supp...

Page 12: ...ing the components 1 Mount the Access Modular Controller AMC2 on the right hand side of the mounting rail 2 Mount the power supply unit on the left hand side of the mounting rail 3 If you are using rechargeable batteries install the batteries at the bottom of the enclosure and secure them with a fixing bracket ...

Page 13: ... Figure 4 1 to the power supply connection labeled OK 3 Attach connector A9 Figure 4 1 to the power supply connection DC 4 Connect the grounding cable A6 Figure 4 1 to the AMC2 grounding point Connecting the AC power cable F 1 Use the cables to connect the three pin connector Figure 1 1 position 11 to the AC connector Figure 4 6 position F4 of the power supply 2 Connect the blue wire to the port m...

Page 14: ... wire to position 3 marked with L Figure 3 2 5 Connect the other end from the brown wire to position 1 marked with L1 Figure 3 2 6 Connect the single blue wire to the position 4 marked with N Figure 3 2 7 Connect the other end from the blue wire to the position 2 marked with N Figure 3 2 Connecting the tamper contact E 1 Mount the micro switch with two screws M2 x 10 mm Figure 1 1 position 6 at th...

Page 15: ...t the ground wire from being accidentally disconnected Connecting the cover grounding cable 1 Connect the mounted grounding cable see position F of Parts included page 6 to the cover grounding point Figure 1 1 position 1 and to the grounding point on the cover of the enclosure 2 Make sure that the screws of the two earthing points are sufficiently tightened Refer to Parts included page 6 Cable ass...

Page 16: ...with one battery left 12 V mode with two batteries right 12 V mode operation using one battery 1 Set the switch of the power supply unit to 12 V 2 Connect B12 to the power supply interface labeled BAT 3 Connect B7b black to the rechargeable negative terminal of the battery 4 Connect B7a red to the rechargeable positive terminal of the battery 5 Attach the bracket to the back of the housing next to...

Page 17: ...power supply unit to 12 V 2 Connect B12 to the power supply interface labeled BAT 3 Connect B7b black to the rechargeable negative terminal of the battery 4 Connect B7a red to the rechargeable positive terminal of the battery 5 Connect B8b black to the second rechargeable negative terminal 6 Connect B8a red to the second rechargeable positive terminal of the battery ...

Page 18: ...the battery cables 1 Set the switch of the power supply unit to 24 V 2 Connect B12 to the power supply interface labeled BAT 3 Connect B7a red to the positive pin of the first rechargeable battery 4 Connect B7b to the negative pin of the second rechargeable battery 5 With cable C1 black connect the negative pin of the first rechargeable battery to the positive pin of the second rechargeable batter...

Page 19: ...AMC2 enclosure with 1 DIN rail Connections en 19 Bosch Security Systems B V 2020 07 V04 F 01U 330 018 7 Attach the bracket to the back of the housing next to the batteries ...

Page 20: ...ss 2 or 3 conductors and all electric light power Class 1 conductors non Class 2 or 3 signaling conductors or medium power network powered broadband communications circuit conductors Figure 3 1 position 1 and 2 Notice When the fuse 5A of cable B power supply battery is blown replace it with a UL listed fuse and reseal the fuse holder with a heat shrink tube Notice If the system is to be UL294 comp...

Page 21: ...s must be assembled by a qualified installer A Power supply AMC2 A A4 A5 A2 A6 A1 A3 Position Description Quantity Size Supplier example A1 Wire 18 AWG black 1 100 mm MediKabel UL Style 1015 121180 08 A2 Wire 18 AWG red 1 100 mm MediKabel UL Style 1015 121180 07 A3 Wire 18 AWG GN YL 1 200 mm MediKabel UL Style 1015 121180 49 A4 Wire 18 AWG blue 4 140 mm MediKabel UL Style 1015 121180 06 A5 End spl...

Page 22: ...04 F 01U 330 018 Bosch Security Systems B V Position Description Quantity Size Supplier example A6 Ring terminal red 4 1 1 Klauke 6204 A7 Power connector of AMC2 1 A8 Power supply control connector 4 pin 1 A9 Power supply DC connector 1 A10 Grounding cable 1 ...

Page 23: ... Size Supplier example B1 Wire 18 AWG black 1 160 mm MediKabel UL Style 1015 121180 08 B2 Wire 18 AWG black 1 240 mm MediKabel UL Style 1015 121180 08 B3 Wire 18 AWG red 1 240 mm MediKabel UL Style 1015 121180 07 B4 End sleeves insulated red 1 5 2 Klauke 172RK B5 Non insulated receptacle 4 8 1 2 Klauke 18203 TYCO 5 160430 7 B6 Non insulated receptacle 4 8 2 5 2 Klauke 18303 TYCO 5 160429 2 B7 Cond...

Page 24: ...se 125V 5A 2AG 1 Littlefuse 0229005 HXP B10 Fuse holder In Line for 5 mm 20 mm fuses 1 Littlefuse 01500274Z B11 Shrink tube 1 50 mm Hellermann Tyson HIS 3 12 4 308 31200 B12 Power supply BAT connector 1 C Battery cable C C1 C2 C2 C C1 C3 C3 Figure 4 2 Battery cable Position Description Quantity Size Supplier example C1 Wire 18 AWG blue 1 250 mm MediKabel UL Style 1015 121180 06 C2 Non insulated re...

Page 25: ... sleeve 4 8 mm 4 Stocko EH 650 110 PA66 Ettinger 12 99 491 D Tamper contact cable D D3 D1 D2 Figure 4 3 Tamper contact cable Position Description Quantity Size Supplier example D1 Wire 22 AWG black 2 400 mm MediKabel UL Style 1007 120227 08 D2 End splice orange 0 5 2 Klauke 169OK D3 Micro switch 1 Saia Burgess V4NST7Y1UL E Power cable E2 E3 E1 E E2 E4 E3 E5 E1 E ...

Page 26: ...5 F1 F Figure 4 4 Power cable Position Description Quantity Size Supplier example E1 Wire 18 AWG blue 1 120 mm MediKabel UL Style 1015 121180 06 E2 Wire 18 AWG brown 1 120 mm MediKabel UL Style 1015 121180 01 E3 End splice insulated red 1 5 4 Klauke 172RK E4 Power supply AC connector E5 Enclosure Power connector ...

Page 27: ...LED power indicator Position Description Quantity Size Supplier example F1 Wire 18 AWG blue 1 120 mm MediKabel UL Style 1015 121180 06 F2 Wire 18 AWG brown 1 120 mm MediKabel UL Style 1015 121180 01 F3 End splice insulated red 1 5 2 Klauke 172RK F4 Twin cable end sleeve grey 2 x 0 75 2 Klauke 8708 F5 LED indicator 125 250V green 1 Bulgin 2950MG9 ...

Page 28: ...28 Appendices AMC2 enclosure with 1 DIN rail 2020 07 V04 F 01U 330 018 Bosch Security Systems B V ...

Page 29: ...AMC2 enclosure with 1 DIN rail Appendices 29 Bosch Security Systems B V 2020 07 V04 F 01U 330 018 ...

Page 30: ...30 Appendices AMC2 enclosure with 1 DIN rail 2020 07 V04 F 01U 330 018 Bosch Security Systems B V ...

Page 31: ......