background image

6

en | System overview

AMC2 enclosure with 1

DIN rail

2020-07 | V04 | F.01U.330.018

Bosch Security Systems B.V.

1.2

Parts included

x3

x1

x1

x1

x2

A

B

E

C

D

x1

F

Summary of Contents for AEC-AMC2-UL01

Page 1: ...AMC2 enclosure with 1 DIN rail AEC AMC2 UL01 en Installation manual ...

Page 2: ......

Page 3: ...onents of the enclosure 4 1 2 Parts included 6 1 3 Cables to be assembled 8 2 Mounting the enclosure 10 3 Connections 11 3 1 Connecting the devices 11 3 2 Connecting the cables 13 3 3 Connections for supporting Universal Power Supply 15 3 3 1 12 V mode operation 16 3 3 2 24 V mode operation 18 4 Appendices 20 4 1 UL requirements 20 4 2 Cable assembly 21 ...

Page 4: ... 7 8 11 12 13 9 5 10 Figure 1 1 Components of the enclosure Position Description 1 Cover grounding point 2 Mounting rail for power supply unit PSU and Access Modular Controller AMC2 3 AMC2 grounding point 4 Cable knock outs for reader and signal cables 5 Temperature sensor bracket 6 Tamper contact 7 Fixing bracket for rechargeable batteries 8 Main grounding point ...

Page 5: ...ith 1 DIN rail System overview en 5 Bosch Security Systems B V 2020 07 V04 F 01U 330 018 Position Description 9 Label 10 Knock out for the power cable connection 11 Three pin connector 12 Bracket for LED 13 Name plate ...

Page 6: ...6 en System overview AMC2 enclosure with 1 DIN rail 2020 07 V04 F 01U 330 018 Bosch Security Systems B V 1 2 Parts included x3 x1 x1 x1 x2 A B E C D x1 F ...

Page 7: ...overview en 7 Bosch Security Systems B V 2020 07 V04 F 01U 330 018 Position Description A Cable ties to secure cables B Three screw anchors S8 and M6 50 screws C Bracket for cable fixing D Fuse and fuse holder E LED F Cover grounding cable ...

Page 8: ... with 1 DIN rail 2020 07 V04 F 01U 330 018 Bosch Security Systems B V 1 3 Cables to be assembled D A C B E F Position Description A Power supply cable AMC2 B Power supply cable battery C Battery cable D Cover contact wired E Power cable ...

Page 9: ...AMC2 enclosure with 1 DIN rail System overview en 9 Bosch Security Systems B V 2020 07 V04 F 01U 330 018 Position Description F Power cable with LED indicator UL required Refer to Cable assembly page 21 ...

Page 10: ...closure aside 5 Drill the holes at the points that you previously marked on the wall 6 Insert the screw anchors in the drilled holes 7 Drive the screws halfway into the top and bottom left screw anchors 8 Hang the enclosure on the wall according to the position of the screw anchors 9 Drive the third screw into the anchor on the bottom right 10 Tighten all screws The enclosure is installed 86 5 mm ...

Page 11: ...C N G L1 BAT RTH Power Supply AMC2 DC RS 485 EXT T OK L N C DC BAT AC 1 2 3 4 5 6 7 1 2 3 4 5 6 1 2 2 1 Figure 3 1 Connections in the enclosure 1 Insert the cables of the device through the knock outs at the top right side wall of the enclosure or through the rear of the enclosure 2 Provide an appropriate disconnect device to the supply line Warning Risk of electric shock Disconnect the mains supp...

Page 12: ...ing the components 1 Mount the Access Modular Controller AMC2 on the right hand side of the mounting rail 2 Mount the power supply unit on the left hand side of the mounting rail 3 If you are using rechargeable batteries install the batteries at the bottom of the enclosure and secure them with a fixing bracket ...

Page 13: ... Figure 4 1 to the power supply connection labeled OK 3 Attach connector A9 Figure 4 1 to the power supply connection DC 4 Connect the grounding cable A6 Figure 4 1 to the AMC2 grounding point Connecting the AC power cable F 1 Use the cables to connect the three pin connector Figure 1 1 position 11 to the AC connector Figure 4 6 position F4 of the power supply 2 Connect the blue wire to the port m...

Page 14: ... wire to position 3 marked with L Figure 3 2 5 Connect the other end from the brown wire to position 1 marked with L1 Figure 3 2 6 Connect the single blue wire to the position 4 marked with N Figure 3 2 7 Connect the other end from the blue wire to the position 2 marked with N Figure 3 2 Connecting the tamper contact E 1 Mount the micro switch with two screws M2 x 10 mm Figure 1 1 position 6 at th...

Page 15: ...t the ground wire from being accidentally disconnected Connecting the cover grounding cable 1 Connect the mounted grounding cable see position F of Parts included page 6 to the cover grounding point Figure 1 1 position 1 and to the grounding point on the cover of the enclosure 2 Make sure that the screws of the two earthing points are sufficiently tightened Refer to Parts included page 6 Cable ass...

Page 16: ...with one battery left 12 V mode with two batteries right 12 V mode operation using one battery 1 Set the switch of the power supply unit to 12 V 2 Connect B12 to the power supply interface labeled BAT 3 Connect B7b black to the rechargeable negative terminal of the battery 4 Connect B7a red to the rechargeable positive terminal of the battery 5 Attach the bracket to the back of the housing next to...

Page 17: ...power supply unit to 12 V 2 Connect B12 to the power supply interface labeled BAT 3 Connect B7b black to the rechargeable negative terminal of the battery 4 Connect B7a red to the rechargeable positive terminal of the battery 5 Connect B8b black to the second rechargeable negative terminal 6 Connect B8a red to the second rechargeable positive terminal of the battery ...

Page 18: ...the battery cables 1 Set the switch of the power supply unit to 24 V 2 Connect B12 to the power supply interface labeled BAT 3 Connect B7a red to the positive pin of the first rechargeable battery 4 Connect B7b to the negative pin of the second rechargeable battery 5 With cable C1 black connect the negative pin of the first rechargeable battery to the positive pin of the second rechargeable batter...

Page 19: ...AMC2 enclosure with 1 DIN rail Connections en 19 Bosch Security Systems B V 2020 07 V04 F 01U 330 018 7 Attach the bracket to the back of the housing next to the batteries ...

Page 20: ...ss 2 or 3 conductors and all electric light power Class 1 conductors non Class 2 or 3 signaling conductors or medium power network powered broadband communications circuit conductors Figure 3 1 position 1 and 2 Notice When the fuse 5A of cable B power supply battery is blown replace it with a UL listed fuse and reseal the fuse holder with a heat shrink tube Notice If the system is to be UL294 comp...

Page 21: ...s must be assembled by a qualified installer A Power supply AMC2 A A4 A5 A2 A6 A1 A3 Position Description Quantity Size Supplier example A1 Wire 18 AWG black 1 100 mm MediKabel UL Style 1015 121180 08 A2 Wire 18 AWG red 1 100 mm MediKabel UL Style 1015 121180 07 A3 Wire 18 AWG GN YL 1 200 mm MediKabel UL Style 1015 121180 49 A4 Wire 18 AWG blue 4 140 mm MediKabel UL Style 1015 121180 06 A5 End spl...

Page 22: ...04 F 01U 330 018 Bosch Security Systems B V Position Description Quantity Size Supplier example A6 Ring terminal red 4 1 1 Klauke 6204 A7 Power connector of AMC2 1 A8 Power supply control connector 4 pin 1 A9 Power supply DC connector 1 A10 Grounding cable 1 ...

Page 23: ... Size Supplier example B1 Wire 18 AWG black 1 160 mm MediKabel UL Style 1015 121180 08 B2 Wire 18 AWG black 1 240 mm MediKabel UL Style 1015 121180 08 B3 Wire 18 AWG red 1 240 mm MediKabel UL Style 1015 121180 07 B4 End sleeves insulated red 1 5 2 Klauke 172RK B5 Non insulated receptacle 4 8 1 2 Klauke 18203 TYCO 5 160430 7 B6 Non insulated receptacle 4 8 2 5 2 Klauke 18303 TYCO 5 160429 2 B7 Cond...

Page 24: ...se 125V 5A 2AG 1 Littlefuse 0229005 HXP B10 Fuse holder In Line for 5 mm 20 mm fuses 1 Littlefuse 01500274Z B11 Shrink tube 1 50 mm Hellermann Tyson HIS 3 12 4 308 31200 B12 Power supply BAT connector 1 C Battery cable C C1 C2 C2 C C1 C3 C3 Figure 4 2 Battery cable Position Description Quantity Size Supplier example C1 Wire 18 AWG blue 1 250 mm MediKabel UL Style 1015 121180 06 C2 Non insulated re...

Page 25: ... sleeve 4 8 mm 4 Stocko EH 650 110 PA66 Ettinger 12 99 491 D Tamper contact cable D D3 D1 D2 Figure 4 3 Tamper contact cable Position Description Quantity Size Supplier example D1 Wire 22 AWG black 2 400 mm MediKabel UL Style 1007 120227 08 D2 End splice orange 0 5 2 Klauke 169OK D3 Micro switch 1 Saia Burgess V4NST7Y1UL E Power cable E2 E3 E1 E E2 E4 E3 E5 E1 E ...

Page 26: ...5 F1 F Figure 4 4 Power cable Position Description Quantity Size Supplier example E1 Wire 18 AWG blue 1 120 mm MediKabel UL Style 1015 121180 06 E2 Wire 18 AWG brown 1 120 mm MediKabel UL Style 1015 121180 01 E3 End splice insulated red 1 5 4 Klauke 172RK E4 Power supply AC connector E5 Enclosure Power connector ...

Page 27: ...LED power indicator Position Description Quantity Size Supplier example F1 Wire 18 AWG blue 1 120 mm MediKabel UL Style 1015 121180 06 F2 Wire 18 AWG brown 1 120 mm MediKabel UL Style 1015 121180 01 F3 End splice insulated red 1 5 2 Klauke 172RK F4 Twin cable end sleeve grey 2 x 0 75 2 Klauke 8708 F5 LED indicator 125 250V green 1 Bulgin 2950MG9 ...

Page 28: ...28 Appendices AMC2 enclosure with 1 DIN rail 2020 07 V04 F 01U 330 018 Bosch Security Systems B V ...

Page 29: ...AMC2 enclosure with 1 DIN rail Appendices 29 Bosch Security Systems B V 2020 07 V04 F 01U 330 018 ...

Page 30: ...30 Appendices AMC2 enclosure with 1 DIN rail 2020 07 V04 F 01U 330 018 Bosch Security Systems B V ...

Page 31: ......

Page 32: ...Bosch Security Systems B V Torenallee 49 5617 BA Eindhoven Netherlands www boschsecurity com Bosch Security Systems B V 2020 ...