Conditions for operation:
The heat pump compressor is activated according the following conditions and according control unit settings
defined.
Conditions for anti-freeze protection (in HP or Standby mode):
Software version after HPAF0211 (-10ºC models) and HPAF0311 (+5ºC models):
Software version before versions
HPAF0211 (-10ºC models) and HPAF0311 (+5ºC models):
Conditions for legionela disinfection:
T
Top
≤
T
set
– 3ºC
(
and
T
bottom
< 60ºC)
T
Top
≥
T
set
(
or
T
bottom
≥
62ºC)
T
Bottom
< 4ºC
Start Up
Stop
Module Anti-Freeze:
Water pump runs for 2 minute
T
Top
≤
5ºC
Tank Anti-Freeze:
Water Pump ON
+
Electrical heater ON till
T
Top
>8ºC
T
Bottom
< 2ºC
Module Anti-Freeze:
Water pump runs for 1 minute
T
Top
≤
20ºC and T
Bottom
< 5ºC
Tank Anti-Freeze:
Water Pump ON
+
Electrical heater ON till
T
Top
>25ºC or T
Bottom
> 10ºC
Water pump is always ON
(for both “Man” or “Aut” selection)