72
en | System Configuration
Conettix Universal Dual Path Communicator
2017.11 | 05 | F.01U.311.207
Installation and Operation Manual
Bosch Security Systems, Inc.
8
System Configuration
Use the parameters in this section to configure the B465 for the Panel Phone Line, for
supervision of the primary power, battery, and enclosure tamper, and for RPS.
8.1
Panel Phone Line Setup
Use the parameters in this section to configure the B465 panel phone line connection.
8.1.1
Panel Reporting Format
Default
:
Auto Detect
Selections
:
–
Auto Detect - the B465 cycles through the handshake tones for each panel reporting
format until the control panel responds. The order is: 2300 Hz, 1400 Hz, Dual Tone, SIA,
Modem II, Modem IIe/IIIa
2
–
Dual Tone - handshake tone for Contact ID (SIA DC-05) reporting format
–
2300 Hz - for pulse formats that require a 2300 Hz handshake tone
–
1400 Hz - for pulse formats that require a 1400 Hz handshake tone
–
SIA - handshake tone for SIA DC-03 format
–
Modem II - handshake tone for Bosch (Radionics) Modem II format
–
Modem IIe/IIIa
2
- handshake tone for Bosch (Radionics) Modem IIe and Modem IIIa
2
formats
Select the handshake tone for the reporting format the control panel connected to the B465
uses.
Notice!
Connected control panel might need the correct handshake sent first
The connected control panel might require that the correct handshake tone is sent first or it
will not send the report. If you selected Auto Detect and the control panel is not sending
reports, select the handshake tone for the reporting format the control panel uses.
USB Menu Location
[4] System Configuration > [1] Panel Phone Line Setup > [1] Panel Reporting Format
8.1.2
Tone Duration (milliseconds)
Default
:
1000 (milliseconds)
Selections
: 200 to 1500 (milliseconds)
The B465 uses this duration for the handshake tones for all reporting formats.
USB Menu Location
[4] System Configuration > [1] Panel Phone Line Setup > [2] Tone Duration
8.2
Primary Power Supervision
8.2.1
Primary Power Source
Default
:
AC
Selections
:
–
AC - the primary power source for the B465 is 16.5 VAC
(D1640 and D1640-CA plug-in transformers, D1640-120WI wire-in transformer)
–
DC - the primary power source for the B465 is 24 VDC.
USB Menu Location
[4] System Configuration > [2] Primary Power Supervision > [1] Primary Power Source