12
Installation Instructions
Vertical Vent Termination
Roof
Flashing
Rain
Cap
Hanger
Strap
Slope up wards
Elbow
1m
Max.
• Terminate at least 1.8m from
the combustion air intake of any
appliance, and 1m from any
other building opening, gas
utility meter, service regulator
etc.
• Terminate the vent system at
least 600mm above but not
more than 2m above the roof
line, or according to the vent
pipe manufacture's instructions.
• Provide vertical support every
3.6m or as required by the vent
pipe manufacturer's instructions.
• Slope the horizontal vent 50mm
upwards for every 1m.