The power circuit to which the device and
the load are connected must be secured
with a circuit breaker in accordance with
EN 60898-1 (trigger characteristics B
or C, max. 16 A rated current, min. 6 kA
breaking capacity, energy limitation class
3). Installation guidelines in accordance
with the applicable national standards, e.g.
VDE 0100 or HD384 or IEC 60364, must
be observed. The circuit breaker must be
easily accessible for the user and labelled
as a disconnecter for the device.
The device is part of the building
installation. The standards and directives
applicable in your country must be
observed during planning and set-up.
Operation of the device is only permitted
at 230 V/50 Hz AC voltage. Work on the
230 V network may only be carried out
by an electrician (relevant standards and
directives of your country). The applicable
accident prevention regulations must be
observed here. To avoid an electric shock
on the device, please switch off the mains
power. Failure to observe the installation
instructions may result in fire or other
hazards.