Installation Manual
Bosch Climate 5000 Series Ducted Type (Medium & High Static) Air Conditioner / Heat Pump
| 29
Bosch Thermotechnology Corp.
|
05.2019
Data subject to change
8.3 Adding Refrigerant
In North America, the standard pipe length is 7.5m (25’). The additional refrigerant
to be charged can be calculated using the following formula:
Additional refrigerant per pipe length
Connective Pipe
Air Purging
Additional Refrigerant
< Standard pipe length
Vacuum Pump
N/A
> Standard pipe length
Vacuum Pump
Liquid Side: Ø 6.35 (ø 0.25”)
Inverter R410A:
(Pipe length – standard length) x 15g/m
(Pipe length – standard length) x 0.16oZ/ft
Liquid Side: Ø 9.52 (ø 0.375”)
Inverter R410A:
(Pipe length – standard length) x 30g/m
(Pipe length – standard length) x 0.32oZ/ft
Table 11
CAUTION: CONTAINS REFRIGERANT
NEVER mix refrigerant types.