Troubleshooting
|
47
6 720 805 218 (2013/02)
SB625WS/SB745WS
10
Troubleshooting
Problem
Cause
Troubleshooting
The boiler does not reach its set temperature.
Heat exchanger dirty.
▶ Clean the flue gas pipes.
Heat exchanger and burner mismatched.
▶ Check specifications and settings.
Insufficient gas flow burner.
▶ Check and adjust the burner.
Control thermostat problem.
▶ Check the functioning of the aquastat.
▶ Check the temperature setting.
The boiler keeps shutting down, and the control
panel warning light comes on.
Control thermostat problem.
▶ Check the functioning of the aquastat.
▶ Check the temperature setting.
▶ Check the electrical wiring.
▶ Check the sensor bulbs.
No water supply.
▶ Check the circuit pressure.
Air in the circuit.
▶ Check the vent valve.
The boiler has reached the set temperature but
the radiators are still cold.
Air in the circuit.
▶ Bleed the circuit.
Pump malfunctioning.
▶ Check/release the pump.
Problem with minimum temperature aquastat (if
present).
▶ Check the temperature setting.
There is a smell of fumes.
Fumes are escaping into the air.
▶ Check that the boiler body is clean.
▶ Check that the flue pipes are clean.
▶ Check that the boiler, flue pipes and flue gas
exhaust stack are all properly sealed.
The safety valve keeps opening.
Excessive pressure in the circuit.
▶ Check the circuit pressure.
▶ Check the functioning of the pressure
reducer.
▶ Check the settings of the pressure reducer.
Problem with heating system expansion vessel.
▶ Check the efficiency of the expansion vessel.
There are traces of condensate on the rear head. Flue gas box seals.
▶ Check the seals between the rear head and
the flue gas box.
Table 21 Troubleshooting