     Control Operations Guide                                                                                                                        Bosch Buderus SSB800SA | SSB1000SA | SSB1000TL Boilers 

 

| 5

 

Bosch Thermotechnology Corp. | 01.2020

             Data subject to change

2     Boiler Parameters

Number

Parameter Name

Description

Default

Min

Max

1

CH Mode

Set Central Heating 

CH Mode

 based upon the desired control strategy for the boiler.

0

0

4

3

CH Set Point

Central Heating Setpoint only applies to 

CH Mode

 #0 ( On/Off using dry contacts) and 

CH Mode

 #3 (Permanent set point 

demand). The value set for 

CH Setpoint

 will be the boiler supply water temperature (system supply for cascade).

140 °F

86 °F

194 °F

109

Calc. SetP. Offset

Factor used in the PID calculation to offset 

CH Setpoint

  up or down.

0 °F

-1.8 °F

1.8 °F

110

CH Min Setpoint

CH Mode

 4 setpoint at 1.5 - 2 VDC.

68 °F

68 °F 

122 °F

111

CH Max Setpoint

CH Mode

 4 setpoint at 9-10 VDC.

194 °F

122 °F

194 °F

5

Boiler Pump Overrun

The post circulation time of the module pump at the end of the heating request. The amount of time in seconds the boiler 
pump contacts will be energized after the demand for heat has ended.

30 sec.

0 sec. 900 sec.

7

CH Hysteresis Up

If the supply temperature reaches a temperature above the 

CH Setpoint 

 plus 

CH Hysteresis up

, then  the burner will be 

switched OFF.

36 °F

0 °F

36 °F

112

CH Hysteresis Down

If the supply temperature reaches a temperature below the 

CH Setpoint 

 minus 

CH Hysteresis down

, then the burner will 

be switched ON.

9 °F

0 °F

36 °F

9

Anti-Cycle Period

The amount of time in seconds the boiler will wait before restarting in 10 second increments.

180 sec. 10 sec. 900 sec.

10

Anti-Cycle Temp. Period Diff

In addition to the 

Anti Cycle Period

 (see above) the boiler will monitor the System Supply Temperature Sensor. If the 

system temperature drops below the 

Anti Cycle Temp. Period Diff

, the 

Anti Cycle Period

  will be ignored and burner will 

start.

28.8 °F

0 °F

36 °F

14

Max Power CH

The Maximum burner power for Central Heating can be limited during operation. 

100%

50%

100%

15

Min Power CH

The Minimum burner power for Central Heating operation can be limited during operation.

1%

1%

30%

19

Design Supply Temp

The water temperature the boiler will supply at 

Design Outdoor Temperature

.

194 °F

86 °F

194 °F

20

Design Outdoor Temp

The outdoor air temperature at which the boiler will supply the 

Design Supply Water Temperature

.

23 °F

-13 °F

77 °F

21

Baseline Supply Temp

The water temperature the boiler will supply at the 

Baseline Outdoor Temperature

.

104°F

68°F

194°F

22

Baseline Outdoor Temp

The outdoor air temperature at which the boiler will target the 

Baseline Supply Temperature

.

68°F

32°F

86°F

23

Design Supply Min Limit

The minimum supply water temperature the heating system will provide to the system. 

86°F

39.2°F 179.6°F

24

Design Supply Max Limit

The maximum supply water temperature the heating system will provide to the system.

194°F

80.6°F

194°F

25

Warm Weather Shut Dn

The temperature above which heating is no longer necessary. All calls for heat will be ignored as long as the outdoor 
temperature remains above the 

Warm Weather Shutdown

 value.

71.6°F

32°F

95°F

26

Boost Temp Increment

Boost Temp Increment

 is active for 

CH Mode

 1. If a call for heat has not been satis

fi

 ed within the period of time de

fi

 ned 

within 

Boost Time Delay

 (see below) the targeted supply temperature will be increased by the value of 

Boost Temp 

Increment

. This process of Boosting supply water will continue until the call for heat is satisi

fi

 ed.

0°F

0°F

54°F

27

Boost Time Delay

Boost Time Delay

 is active only for 

CH Mode

 1.  If a call for heat has not been satis

fi

 ed within the time limit (in minutes) 

de

fi

 ned within 

Boost Time Delay

, the supply water temperature will be increased by 

Boost Temp Increment

 (see above). 

Supply water temperature increases again if the call for heat still is not satis

fi

  ed in another time increment.

20 min.

1 min. 120 min.

28

Night Setback Temp

Only available for 

CH Modes

 #2 and #3.  The value the heating curve will be reset as long as contacts #11 & #12 are "open" 

(i.e. via an external clock timer or switch).

18°F

0°F

90°F

35

DHW Mode

When an Indirect tank is present in the system set 

DHW Mode

 to 

1

 when using the factory supplied 10K ohm sensor or set 

to 

 if using a third-party aquastat.  Default value is 

0

 (Off).

0

0

2

113

Max Power DHW

The maximum power for DHW can be limited during operation.   

50%

50%

100%

114

Min Power DHW

The minimum power for DHW operation can be limited during operation. 

1%

1%

30%

36

DHW Tank Hyst. Down

The necessary temperature drop of the indirect tank temperature needed before the boiler will begin to recover the tank. 
Only active when 

DHW Mode

 (par. #35) is set to 

 and a 10k ohm sensor is used.

9 °F

0 °F

36 °F

37

DHW Tank Hyst. Up

The necessary temperature drop of the indirect tank temperature needed before the boiler will begin to recover the tank. 
Only active when 

DHW Mode

 (par. #35) is set to 

 and a 10k ohm sensor is used.

9 °F

0 °F%

36 °F

38

DHW Tank Supply Extra

The Target Supply Water temperature to the indirect coil is equal to 

DHW Tank Setpoint

 (par. #48) plus 

DHW Tank Supply 

Extra

.  

27 °F

0 °F

54 °F

42

DHW Priority

Default setting is

 

Time

Time - DHW has priority to CH during 

DHW Max Priority Time

*

Off - CH always has priority to DHW
On - DHW always has priority to CH
Parallel - DHW always has priority to CH. CH pump can be started if CH has a request and 

CH setpoint

 > supply for DHW

TIME

N/A

N/A

Table 1

Summary of Contents for Buderus SSB

Page 1: ...rations SSB800SA SSB1000SA SSB1000TL Control Operations Guide WARNING the heating system can cause personal injury and property damage Follow these instructions precisely If you require assistance or further information contact a licensed ...

Page 2: ...2 Bosch Buderus SSB800SA SSB1000SA SSB1000TL Boilers Control Operations Guide 01 2020 Bosch Thermotechnology Corp Data subject to change ...

Page 3: ... 4 1 2 Safety 4 2 Boiler Parameters 5 3 Module Cascade Settings 7 4 Boiler Cascade Settings 8 5 Heating Modes 9 5 1 Central Heating CH Mode 9 5 1 1 Central Heating Mode 0 9 5 1 2 Central Heating Mode 1 10 5 1 3 Central Heating Mode 2 11 5 1 4 Central Heating Mode 3 12 5 1 5 Central Heating Mode 4 13 6 Domestic Hot Water 14 6 1 Domestic Hot Water Operation 14 7 Boiler Cascade Settings 15 7 1 Cascad...

Page 4: ... avoided will result in death or serious injury WARNING indicates a hazardous situation which if not avoided could result in death or serious injury CAUTION indicates a hazardous situation which if not avoided could result in minor to moderate injury NOTICE is used to address practices not related to personal injury Important information This symbol indicates important information where there is n...

Page 5: ... F 32 F 86 F 23 Design Supply Min Limit The minimum supply water temperature the heating system will provide to the system 86 F 39 2 F 179 6 F 24 Design Supply Max Limit The maximum supply water temperature the heating system will provide to the system 194 F 80 6 F 194 F 25 Warm Weather Shut Dn The temperature above which heating is no longer necessary All calls for heat will be ignored as long as...

Page 6: ... N A N A 123 Prog Input 8 Factory Setting Do Not Change N A N A N A 124 Prog Input RT Factory Setting Do Not Change N A N A N A 125 Prog Output 1 Factory Setting Do Not Change N A N A N A 126 Prog Output 2 Factory Setting Do Not Change N A N A N A 127 Prog Output 3 Factory Setting Do Not Change N A N A N A 128 Prog Output 4 Factory Setting Do Not Change N A N A N A 129 Flow Sensor Factory Setting ...

Page 7: ...rate at temperatures greater than or less than the desired Target System Supply Temperature The operating range in which the modules are allowed to adjust the individual module supply temperatures is defined by the Max Setp Offset Down and Max Setp Offset Up parameter 80 values Each dependent module will display a Calculated Setpoint temperature on the display which will be within this Off set Ran...

Page 8: ... Quick Stop Next 14 4 F 0 F 108 F 167 Number Of Boilers The amount of boilers in the cascade 1 1 8 168 Power Mode Power mode 0 Power control disabled each boiler modulates based on the system setpoint Power mode 1 Power control algorithm to have a minimum amount of boilers active Power mode 2 Power control algorithm to have a maximum amount of boilers active Power mode 3 Power control algorithm to...

Page 9: ...the boiler using dry contacts 9 and 10 CH Mode 0 Boiler demand is generated thru a call for heat on low voltage contacts 9 and 10 dry contacts only The Boiler will then target a temperature equal to CH Setpoint par 3 at the Supply Temperature Sensor CentralHeating CH Mode Description Set these Parameters Parameter Description Default Range CH Mode 0 Setpoint control using dry contacts TT 1 CH Mode...

Page 10: ...F 1 8 1 8 F 5 Boiler Pump Overrun 30 sec 0 900 sec 7 CH Hysteresis Up 36 F 0 36 F 112 CH Hysteresis Down 9 F 0 36 F 9 Anti cycle Period 180 sec 10 900 sec 10 Anti cycle Temp Diff 28 8 F 0 36 F 14 Max Power CH 100 50 100 15 Min Power CH 1 1 30 19 Design Supply Temp 194 F 86 194 F 20 Design Outdoor Temp 23 F 13 77 F 21 Baseline Supply Temp 104 F 68 194 F 22 Baseline Outdoor Temp 68 F 32 86 F 23 Desi...

Page 11: ... contacts are open using a clock or switch CentralHeating CH Mode Description Set these Parameters Parameter Description Default Range CH Mode 2 Full Outdoor reset with no heat demand 1 CH Mode 0 0 5 109 Calc Set point Offset 0 F 1 8 1 8 F 5 Boiler pump overrun 30 sec 0 900 sec 7 CH Hysteresis Up 36 F 0 36 F 112 CH Hysteresis Down 9 F 0 36 F 9 Anti cycle Period 180 sec 10 900 sec 10 Anti cycle Tem...

Page 12: ...ed to the curve when 9 and 10 contacts are open using a clock or switch CentralHeating CH Mode Description Set these Parameters Parameter Description Default Range CH Mode 3 Permanent Setpoint Demand 1 CH Mode 0 0 5 3 CH Setpoint 140 F 86 194 F 109 Calc Set point Offset 0 F 1 8 1 8 F 5 Boiler pump overrun 30 sec 0 900 sec 7 CH Hysteresis up 36 F 0 36 F 112 CH Hysteresis down 9 F 0 36 F 9 Anti cycl...

Page 13: ...curred The Boiler and CH pump contacts will remain energized as long as the voltage from the BMS remains greater than 1 VDC Figure 2 OFF 1 0 1 5 2 0 ON 9 Modulation CH Setpoint Max CH Setpoint Min Voltage Vdc Set Point F CentralHeating CH Mode Description Set these Parameters Parameter Description Default Range CH Mode 4 Analog 0 10 VDC Setpoint Control 1 CH Mode 0 0 5 109 Calc Setpoint Offset 0 F...

Page 14: ...ter temperature falls DHW Tank Hyst Down degrees below the desired set temperature for hot water the boiler will begin to heat the indirect tank with a setpoint of DHW Tank Setpoint plus DHW Tank Supply Extra The system will stop heating the tank when it reaches DHW Tank Setpoint plus DHW Tank Hyst Up Using a field supplied aquastat 1 Wire your field supplied aquastat to 7 and 8 on low voltage ter...

Page 15: ...ntrol board 3 Using 18 2 wire connect all of the boilers in the cascade using the low voltage contacts 1 and 2 on each boilers control board Note the polarity 4 Turn the power on to all boilers a Press Menu Settings Boiler Settings b Using the Arrow Key pad enter the passcode 0300 to enter the service level of the control c Boiler Cascade Settings 5 Scroll to each of the following parameters and a...

Page 16: ...United States and Canada Bosch Thermotechnology Corp 65 Grove Street Watertown MA 02472 Tel 866 642 3198 Fax 954 776 5529 www boschheatingandcooling com BTC 438002103 A 01 2020 ...

Reviews: