background image

8  |

  

Bosch Buderus SSB800SA | SSB1000SA | SSB1000TL Boilers                                                                                                                    Control Operations Guide 

01.2020 | Bosch Thermotechnology Corp.

Data subject to change

4     Boiler Cascade Settings

Number

Parameter Name

Description

Default

Min

Max

73

Boiler Address

Set boiler address i.e. Stand-Alone, Managing, Dependent 1....7

MANAGING

0

16

156

Permit Emergency Mode

Enable 

Emergency Mode

 in a multiple boiler cascade installation to ensure that any dependent boiler can operate 

independently should communication with the managing boiler be interrupted or the managing boiler loses 
communication with the supply sensor. The boiler will operate at a predetermined 

Emergency Setpoint 

 which is  

set using Parameter #157.

YES

NO YES

157

Emergency Setpoint

Emergency Setpoint

 is the 

fi

  xed set point which a boiler will operate at within a cascade installation if that boiler 

has lost communication with the Managing boiler or the Managing boiler loses communication with the supply 
sensor. Parameter #156 must be “Yes” on each dependent boiler and 

Emergency Setpoint 

 set for the desired 

Emergency Temperature at which the boiler is to operate.

158 °F

68 °F 

194 °F

158

Delay Per Start Next Blr

See 

Hyst Down Start Boiler

.

1275 sec. 

0 sec.

1275 sec.

159

Delay Per Stop Next Blr

See 

Hyst Up Stop Boiler

.

1275 sec.

0 sec.

1275 sec.

160

Delay Quick Start Next 

See 

Hyst Down Quick Start

.

400 sec.

0 sec. 

1275 sec.

161

Delay Quick Stop Next 

See 

Hyst Up Quick Stop

.

240 sec. 

0 sec. 

1275 sec.

162

Hyst Down Start Boiler

If the system temperature is 

Hyst Down Start Boiler

  degrees below the system set point the boilers are started at 

intervals of 

Delay Per Start Next Blr

.

9 °F

0 °F 

72 °F

163

Hyst Up Stop Boiler

If the system temperature is 

Hyst Up Stop Boiler

  degrees above the system set poin tthe boilers are stopped at 

intervals of 

Delay Per Start Next Blr

.

3.6 °F 

0 °F 

72 °F

164

Hyst Down Quick Start

If the system temperature is 

Hyst Down Quick Start

  degrees below the system set point the boilers are started at 

intervals of 

Delay Quick Start Next

.

18 °F 

0 °F 

72 °F

165

Hyst Up Quick Stop

If the system temperature 

Hysteresis Up Quick Stop

  degrees is above the system set point the boilers are stopped 

at intervals of 

Delay Quick Stop Next

.

7.2 °F

0 °F

72 °F

166

Hyst Up Stop All

If the system temperature is 

Hyst Up Quick Stop

 degrees above the system set point the boilers are stopped at 

intervals of 

Delay Quick Stop Next

14.4 °F

0 °F

108 °F

167

Number Of Boilers

The amount of boilers in the cascade.

1

1

8

168

Power Mode

Power mode 0: Power control disabled, each boiler modulates based on the system setpoint.
Power mode 1: Power control algorithm to have a minimum amount of boilers active.
Power mode 2: Power control algorithm to have a maximum amount of boilers active.
Power mode 3: Power control algorithm to have a balanced amount of boilers active.

2

0

3

169

Max Setp Offset Down

In order to achieve the desired Target System Supply Temperature during a call for heat the boilers may need to 
operate at temperatures greater than or less than the desired Target System Supply Temperature. The operating 
range in which the boilers are allowed to adjust the individual boiler supply temperatures is de

fi

 ned by the

 Max Setp 

Offset Down

 and 

Max Setp Offset Up

 (parameter #170) values. Each dependent boiler will display a “Calculated 

Setpoint” temperature on the display which will be within this Off set Range either above or below the overall Target 
System Supply Temperature.

0 °F

0 °F

72 °F

170

Max Setp Offset Up

See Parameter #169 for explanation of 

Max Setp Offset Down

 and 

Max Setp Offset Up

.

36 °F

0 °F 

72 °F

171

Start Mod Delay Fact

The Managing boiler will calculate the difference between the System Target Setpoint and the measured System 
Supply Temperature once a period of time equal to 

Delay Period Start Next Boiler

 x 

Start Modulation Delay 

Factor 

has passed.

20

0

255

172

Next Boiler Start Rate

The percentage of power a boiler must reach before the Managing boiler will begin the process of bringing on the 
next boiler within the cascade. See Parameter#158 for further information on the amount of time which must pass 
at this power percentage before the next boiler in the cascade rotation is enabled.

80%

10%

100%

173

Next Boiler Stop Rate

The percentage of power a boiler must reach before the Managing boiler will begin the process of turning off the last 
boiler enabled within the cascade rotation sequence. See Parameter #159 for further information on the amount of 
time which must pass at this power percentage before a boiler is turned off.

25%

10%

100%

174

Boiler Rotation Interval

Number of days selectable.

5 DAYS

0 DAYS

30 DAYS

175

First Boiler To Start

First boiler in cascade that will start.

1

1

8

180

Pwr Mode 2 Min Power

Minimum average burner power setting.

20%

0%

100%

181

Pwr Mode 2 Hysteresis

Hysteresis for the minimum average boiler power setting.

40%

0%

100%

182

Post-Pump Period

Factory setting - Do Not Change

N/A

N/A

N/A

Table 3

Summary of Contents for Buderus SSB

Page 1: ...rations SSB800SA SSB1000SA SSB1000TL Control Operations Guide WARNING the heating system can cause personal injury and property damage Follow these instructions precisely If you require assistance or further information contact a licensed ...

Page 2: ...2 Bosch Buderus SSB800SA SSB1000SA SSB1000TL Boilers Control Operations Guide 01 2020 Bosch Thermotechnology Corp Data subject to change ...

Page 3: ... 4 1 2 Safety 4 2 Boiler Parameters 5 3 Module Cascade Settings 7 4 Boiler Cascade Settings 8 5 Heating Modes 9 5 1 Central Heating CH Mode 9 5 1 1 Central Heating Mode 0 9 5 1 2 Central Heating Mode 1 10 5 1 3 Central Heating Mode 2 11 5 1 4 Central Heating Mode 3 12 5 1 5 Central Heating Mode 4 13 6 Domestic Hot Water 14 6 1 Domestic Hot Water Operation 14 7 Boiler Cascade Settings 15 7 1 Cascad...

Page 4: ... avoided will result in death or serious injury WARNING indicates a hazardous situation which if not avoided could result in death or serious injury CAUTION indicates a hazardous situation which if not avoided could result in minor to moderate injury NOTICE is used to address practices not related to personal injury Important information This symbol indicates important information where there is n...

Page 5: ... F 32 F 86 F 23 Design Supply Min Limit The minimum supply water temperature the heating system will provide to the system 86 F 39 2 F 179 6 F 24 Design Supply Max Limit The maximum supply water temperature the heating system will provide to the system 194 F 80 6 F 194 F 25 Warm Weather Shut Dn The temperature above which heating is no longer necessary All calls for heat will be ignored as long as...

Page 6: ... N A N A 123 Prog Input 8 Factory Setting Do Not Change N A N A N A 124 Prog Input RT Factory Setting Do Not Change N A N A N A 125 Prog Output 1 Factory Setting Do Not Change N A N A N A 126 Prog Output 2 Factory Setting Do Not Change N A N A N A 127 Prog Output 3 Factory Setting Do Not Change N A N A N A 128 Prog Output 4 Factory Setting Do Not Change N A N A N A 129 Flow Sensor Factory Setting ...

Page 7: ...rate at temperatures greater than or less than the desired Target System Supply Temperature The operating range in which the modules are allowed to adjust the individual module supply temperatures is defined by the Max Setp Offset Down and Max Setp Offset Up parameter 80 values Each dependent module will display a Calculated Setpoint temperature on the display which will be within this Off set Ran...

Page 8: ... Quick Stop Next 14 4 F 0 F 108 F 167 Number Of Boilers The amount of boilers in the cascade 1 1 8 168 Power Mode Power mode 0 Power control disabled each boiler modulates based on the system setpoint Power mode 1 Power control algorithm to have a minimum amount of boilers active Power mode 2 Power control algorithm to have a maximum amount of boilers active Power mode 3 Power control algorithm to...

Page 9: ...the boiler using dry contacts 9 and 10 CH Mode 0 Boiler demand is generated thru a call for heat on low voltage contacts 9 and 10 dry contacts only The Boiler will then target a temperature equal to CH Setpoint par 3 at the Supply Temperature Sensor CentralHeating CH Mode Description Set these Parameters Parameter Description Default Range CH Mode 0 Setpoint control using dry contacts TT 1 CH Mode...

Page 10: ...F 1 8 1 8 F 5 Boiler Pump Overrun 30 sec 0 900 sec 7 CH Hysteresis Up 36 F 0 36 F 112 CH Hysteresis Down 9 F 0 36 F 9 Anti cycle Period 180 sec 10 900 sec 10 Anti cycle Temp Diff 28 8 F 0 36 F 14 Max Power CH 100 50 100 15 Min Power CH 1 1 30 19 Design Supply Temp 194 F 86 194 F 20 Design Outdoor Temp 23 F 13 77 F 21 Baseline Supply Temp 104 F 68 194 F 22 Baseline Outdoor Temp 68 F 32 86 F 23 Desi...

Page 11: ... contacts are open using a clock or switch CentralHeating CH Mode Description Set these Parameters Parameter Description Default Range CH Mode 2 Full Outdoor reset with no heat demand 1 CH Mode 0 0 5 109 Calc Set point Offset 0 F 1 8 1 8 F 5 Boiler pump overrun 30 sec 0 900 sec 7 CH Hysteresis Up 36 F 0 36 F 112 CH Hysteresis Down 9 F 0 36 F 9 Anti cycle Period 180 sec 10 900 sec 10 Anti cycle Tem...

Page 12: ...ed to the curve when 9 and 10 contacts are open using a clock or switch CentralHeating CH Mode Description Set these Parameters Parameter Description Default Range CH Mode 3 Permanent Setpoint Demand 1 CH Mode 0 0 5 3 CH Setpoint 140 F 86 194 F 109 Calc Set point Offset 0 F 1 8 1 8 F 5 Boiler pump overrun 30 sec 0 900 sec 7 CH Hysteresis up 36 F 0 36 F 112 CH Hysteresis down 9 F 0 36 F 9 Anti cycl...

Page 13: ...curred The Boiler and CH pump contacts will remain energized as long as the voltage from the BMS remains greater than 1 VDC Figure 2 OFF 1 0 1 5 2 0 ON 9 Modulation CH Setpoint Max CH Setpoint Min Voltage Vdc Set Point F CentralHeating CH Mode Description Set these Parameters Parameter Description Default Range CH Mode 4 Analog 0 10 VDC Setpoint Control 1 CH Mode 0 0 5 109 Calc Setpoint Offset 0 F...

Page 14: ...ter temperature falls DHW Tank Hyst Down degrees below the desired set temperature for hot water the boiler will begin to heat the indirect tank with a setpoint of DHW Tank Setpoint plus DHW Tank Supply Extra The system will stop heating the tank when it reaches DHW Tank Setpoint plus DHW Tank Hyst Up Using a field supplied aquastat 1 Wire your field supplied aquastat to 7 and 8 on low voltage ter...

Page 15: ...ntrol board 3 Using 18 2 wire connect all of the boilers in the cascade using the low voltage contacts 1 and 2 on each boilers control board Note the polarity 4 Turn the power on to all boilers a Press Menu Settings Boiler Settings b Using the Arrow Key pad enter the passcode 0300 to enter the service level of the control c Boiler Cascade Settings 5 Scroll to each of the following parameters and a...

Page 16: ...United States and Canada Bosch Thermotechnology Corp 65 Grove Street Watertown MA 02472 Tel 866 642 3198 Fax 954 776 5529 www boschheatingandcooling com BTC 438002103 A 01 2020 ...

Reviews: