background image

22

 

Climate 5000 MS – 6720887246 (2018/04)

 Information on Servicing

 

labelling and signs that are illegible shall be corrected;

 

refrigeration pipe or components are installed in a position where 

they are unlikely to be exposed to any substance which may corrode 

refrigerant containing components, unless the components are 

constructed of materials which are inherently resistant to being 

corroded or are suitably protected against being corroded.

9.  Checks to electrical devices

Repair and maintenance to electrical components shall include initial 

safety checks and component inspection procedures. If a fault exists that 

could compromise safety, then no electrical supply shall be connected 

to the circuit until it is satisfactorily dealt with. If the fault cannot be 

corrected immediately and it is necessary to continue operation, an 

adequate temporary solution shall be used. This shall be reported to the 

owner of the equipment so that all parties are advised.

Initial safety checks shall include:

 

that capacitors are discharged: this shall be done in a safe manner 

to avoid possibility of sparking

 

that there no live electrical components and that wiring is not 

exposed while charging, recovering or purging the system;

 

that there is continuity of earth bonding.

10.  Repairs to sealed components

10.1  During repairs to sealed components, all electrical supplies shall 

be disconnected from the equipment being worked upon prior to 

any removal of sealed covers, etc. If it is absolutely necessary to 

have an electrical supply to equipment during servicing, then a 

permanently operating form of leak detection shall be located at 

the most critical point to warn of a potentially hazardous situation.

10.2  Particular attention shall be paid to the following to ensure that 

when working on electrical components, the casing is not altered in 

such a way that the level of protection is affected. This shall include 

damage to cables, excessive number of connections, terminals not 

made to original specification, damage to seals, incorrect fitting of 

glands, etc.

 

Ensure that the apparatus is mounted securely.

 

Ensure that seals or sealing materials have not degraded such 

that they no longer serve the purpose of preventing the ingress 

of, flammable atmospheres. Replacement parts shall be in 

accordance with the manufacturer s specifications.

NOTE:

The use of silicon sealant may inhibit the effectiveness of some types of 

leak detection equipment. Instrinsically safe components do not have to 

be isolated prior to working on them.

11.  Repair to intrinsically safe components

Do not apply any permanent inductive or capacitance loads to the 

circuit without ensuring that this will not exceed the permissible voltage 

and current permitted for the equipment in use. Intrinscially safe 

components are the only types that can be worked on while live in the 

presence of a flammable atmosphere. The test apparatus shall be at the 

correct rating.
Replace components only with parts specified by the manufacturer. 

Other parts may result in the ignition of refrigerant in the atmosphere 

from a leak.

12.  Cabling

Check that cabling will not be subject to wear, corrosion, excessive 

pressure, vibration, cutting by sharp edges or any other adverse 

environmental effects. The check shall also take into account the effects 

of aging or continual vibration from sources such as compressors or 

fans.

13.  Detection of flammable refrigerants

Under no circumstances shall potential sources of ignition be used in the 

search for or detection of refrigerant leaks. A halide torch (or any other 

detector using a naked flame) may not be used.

14.  Leak detection methods

The following leak detection methods are deemed acceptable for 

systems containing flammable refrigerants. Electronic leak detectors 

shall be used to detect flammable refrigerants, but their sensitivity may 

not be adequate, or may need re-calibration. (Detection equipment 

shall be calibrated in a refrigerant-free area.) Ensure that the detector 

is not a potential source of ignition and is suitable for the refrigerant. 

Leak detection equipment shall be set at a percentage of the LFL of the 

refrigerant and shall be calibrated to the refrigerant employed and the 

appropriate percentage of gas (25% maximum). Leak detection fluids 

are suitable for use with most refrigerants, but the use of detergents 

containing chlorine shall be avoided. Chlorine may react with the 

refrigerant and corrode the copper pipe-work.
If a leak is suspected, all naked flames shall be removed or extinguished. 

If a leakage of refrigerant is found which requires brazing, all of the 

refrigerant shall be recovered from the system, or isolated (by means of 

shut off valves) in a part of the system remote from the leak. Oxygen-free 

nitrogen (OFN) shall then be purged through the system both before and 

during the brazing process.

15.  Removal and evacuation

When breaking into the refrigerant circuit to make repairs for any 

other purpose, conventional procedures shall be used. However, it is 

important that best practice is followed since flammability needs to be 

considered. The following procedure shall be adhered to:
1)  remove refrigerant;
2)  purge the circuit with inert gas;
3)  evacuate;
4)  purge again with inert gas;
5)  open the circuit by cutting or brazing.
The refrigerant charge shall be recovered into the correct recovery 

cylinders. The system shall be flushed with OFN to render the unit safe. 

You may have to repeat this process several times. Compressed air or 

oxygen shall not be used for this task.
Flushing shall be achieved by breaking the vacuum in the system with 

OFN and by continuing to fill until the working pressure is achieved. Then 

vent  to atmosphere, and finally pull down to a vacuum. This process 

shall be repeated until no refrigerant is within the system anymore.
When the final OFN charge is used, the system shall be vented down 

to atmospheric pressure so that work can take place. This operation is 

absolutely vital if brazing operation on the pipe-work is to take place.
Ensure that the outlet for the vacuum pump is not closed to any ignition 

sources and that ventilation is available.

16.  Charging procedures

In addition to conventional charging procedures, the following 

requirements shall be adhered to:

 

Ensure that contamination of different refrigerants does not occur 

when using charging equipment. Hoses or lines shall be as short as 

possible to minimise the amount of refrigerant contained in them.

 

Cylinders shall be kept upright.

 

Ensure that the refrigeration system is earthed prior to charging the 

system with refrigerant.

 

Label the system when charging is complete (if not already).

 

Extreme care shall be taken not to overfill the refrigeration system.

Summary of Contents for Climate 5000 MS 18

Page 1: ...OU OUE Installation Manual IMPORTANT NOTE Read this manual carefully before installing or operating your new air conditioning unit Make sure to save this manual for future reference This manual only describes the installation of outdoor units When installing an indoor unit refer to the installation manual of the indoor unit ...

Page 2: ...ion 9 6 3 Notes on Drilling Hole in Wall 9 6 4 When Selecting 7 1KW units 9 7 Refrigerant Piping Connection 10 8 Wiring 12 8 1 Outdoor Unit Wiring 13 8 2 Wiring Figure 14 9 Air Evacuation 18 9 1 Evacuate Instructions 18 9 2 Note on Adding Refrigerant 18 9 3 Safety and Leakage Check 19 10 Test Run 20 11 Function of Automatic Wiring Piping Correction 20 12 European Disposal Guidelines 21 13 Informat...

Page 3: ...n Ø1 2 in Ø3 4 in Owner s manual 1 Installation manual 1 Transfer connector packed with the indoor or outdoor unit depending on models NOTE Pipe size may differ from appliance to appliance To meet different pipe size requirements sometimes the pipe connections need a transfer connector installed on the outdoor unit 1 one piece one indoor unit 1 5 1 5 pieces for outdoor unit depending on models Mag...

Page 4: ...ssment specification Servicing shall only be performed as recommended by the equipment manufacturer Maintenance and repair requiring the assistance of other skilled personnel shall be carried out under the supervision of the qualified personnel in the use of flammable refrigerants The appliance shall be stored so as to prevent mechanical damage from occurring Keep ventilation openings clear of obs...

Page 5: ... fire CAUTION This symbol shows that the opera tion manual should be read carefully CAUTION This symbol shows that service personnel should be handling this equipment with reference to the installation manual CAUTION CAUTION This symbol shows that information is available such as the operating manual or installation manual 3 Installation Overview INSTALLATION ORDER L N 1 2 3 MC MC 4 5 Install the ...

Page 6: ... Four One Five More than 12 cm More than 12 cm More than 12 cm More than 12 cm More than 12 cm More than 12 cm Morethan 60cm More than 30 cm Morethan200cm Morethan200cm More than 60 cm More than 30 cm More than 30 cm M o r e t h a n 3 0 c m More than 60 cm More than 60 cm Air filter Air filter Air filter Air out Air out Safety Precautions CAUTION To prevent wall damage use a stud finder to locate ...

Page 7: ...s f f Place the outdoor unit as close to the indoor unit as possible f f Ensure that there is enough room for installation and maintenance f f The air inlet and outlet must not be obstructed or exposed to strong wind f f Ensure the location of the unit will not be subject to snowdrifts accumulation of leaves or other seasonal debris f f The installation area must be dry and well ventilated f f The...

Page 8: ...and maintenance Split Type Outdoor Unit Refer to Fig 7 8 9 12 and Table 5 W H Fig 7 W H Fig 8 D A H Fig 9 OutdoorUnitDimensions WxHxD MountingDimensions DistanceA DistanceB 760x590x285 530 290 810x558x310 549 325 845x700x320 560 335 900x860x315 590 333 945x810x395 640 405 990x965x345 624 366 938x1369x392 634 404 900x1170x350 590 378 800x554x333 514 340 845x702x363 540 350 946x810x420 673 403 946x8...

Page 9: ...2 B do the following 1 Insert the drain joint into the hole in the base pan of the unit The drain joint will click in place 2 Connect a drain hose extension not included to the drain joint to redirect water from the unit during heating mode NOTE Ensure the water drains to a safe location where it will not cause water damage or become a slipping hazard A B Seal Seal Drain joint Base pan hole of out...

Page 10: ...t gas is both toxic and flammable Ensure there is no refrigerant leakage after completing the installa tion work Refrigerant Piping Connection Instructions CAUTION The branching pipe must be installed horizontally An angle of more than 10 may cause malfunction DO NOT install the connecting pipe until both indoor and outdoor units have been installed Insulate both the gas and liquid piping to preve...

Page 11: ... clockwise until the pipe is fully flared Flare the pipe in accordance with the dimensions shown in table 8 Pipe gauge Tightening torque Flare dimension A Unit mm Inch Flare shape Min Max Ø 6 4 18 20 N m 183 204 kgf cm 8 4 8 7 Flare shape R0 4 0 8 45 2 90 4 A Fig 18 Ø 9 5 25 26 N m 255 265 kgf cm 13 2 13 5 Ø 12 7 35 36 N m 357 367 kgf cm 16 2 16 5 Ø 15 9 45 47 N m 459 480 kgf cm 19 2 19 7 Ø 19 1 6...

Page 12: ... for this unit DO NOT plug another appliance or charger into the same outlet If the electrical circuit capacity is not enough or there is a defect in the electrical work it can lead to shock fire unit and property damage Connect the power cable to the terminals and fasten it with a clamp An insecure connection may cause fire Ensure that all wiring is done correctly and the control board cover is p...

Page 13: ...abels on the terminal block and firmly screw the u lug of each wire to its corresponding terminal 4 Clamp down the cable with designated cable clamp 5 Insulate unused wires with electrical tape Keep them away from any electrical or metal parts 6 Reinstall the cover of the electric control box Harmonic Declaration The equipment M4OB 36HFN8 Q complies with IEC 61000 3 12 provided that the short circ...

Page 14: ...through the lower line outlet of the cord clamp One twin models L A S A N A L B N B S B W L N L 1 POWER POWER POWER POWER SUPPLY POWER POWER Model B Model A Model E Model F Model G Model C Model D POWER OPTIONAL OPTIONAL OPTIONAL OPTIONAL OPTIONAL OPTIONAL OPTIONAL OPTIONAL OPTIONAL OPTIONAL OPTIONAL OPTIONAL OPTIONAL OPTIONAL OPTIONAL OPTIONAL OPTIONAL OPTIONAL OPTIONAL OPTIONAL OPTIONAL TO A TO ...

Page 15: ...to the following figures if end users wish to perform their own wiring One three models L A N A S A L B N B S B L C N C S C N L OPTIONAL OPTIONAL OPTIONAL OPTIONAL OPTIONAL OPTIONAL OPTIONAL OPTIONAL OPTIONAL OPTIONAL OPTIONAL OPTIONAL OPTIONAL OPTIONAL OPTIONAL OPTIONAL OPTIONAL OPTIONAL OPTIONAL OPTIONAL OPTIONAL OPTIONAL OPTIONAL OPTIONAL POWER POWER POWER SUPPLY POWER POWER POWER TO A TO A TO ...

Page 16: ...PTIONAL OPTIONAL OPTIONAL OPTIONAL OPTIONAL OPTIONAL OPTIONAL OPTIONAL POWER POWER POWER POWER POWER POWER SUPPLY TO A TO A TO A TO A TO A TO A TO B TO B TO B TO B TO B TO B TO C TO C TO C TO C TO C TO C TO D TO D TO D TO D TO D TO D Model A Model C Model C Model B Model D Model D Y G Y G Y G Y G Fig 26 One five models OPTIONAL OPTIONAL OPTIONAL OPTIONAL OPTIONAL OPTIONAL OPTIONAL OPTIONAL OPTIONA...

Page 17: ...ly fastened Check the specifications for the power source Confirm that electrical capacity is suffi cient Confirm that starting voltage is maintained at more than 90 percent of the rated voltage marked on the name plate Confirm that the cable thickness is as specified in the power source specifications Always install an earth leakage circuit breaker in wet or moist areas The following can be cause...

Page 18: ...ge in system pressure there may be a gas leak 8 Insert a hexagonal wrench into the packed valve high pressure valve and open the valve by turning the wrench 1 4 counterclockwise Listen for the gas to exit the system then close the valve after 5 seconds Flare nut Valve body Valve stem Cap Fig 30 9 Watch the pressure gauge for one minute to make sure that there is no change in pressure It should rea...

Page 19: ...ation Cover the following areas 1 Insulated resistance The insulated resistance must be more than 2MО 2 Earthing work After finishing earthing work measure the earthing resistance by visual detection using the earthing resistance tester Make sure the earthing resistance is less than 4О 3 Electrical leakage check perform test while unit is on During a test operation after completed installation the...

Page 20: ...s unimpeded and draining smoothly g Ensure there is no vibration or abnormal noise during operation 5 For the Outdoor Unit a Check to see if the refrigeration system is leaking b Ensure there is no vibration or abnormal noise during operation c Ensure the wind noise and water generated by the unit do not disturb the surrounding area or pose a safety hazard NOTE If the unit malfunctions or does not...

Page 21: ...ble refrigerants i e no sparking that it is adequately sealed and intrinsically safe 5 Presence of fire extinguisher If any hot work is to be conducted on the refrigeration equipment or any associated parts appropriate fire extinguishing equipment shall be available Have a dry power or CO2 fire extinguisher next to the charging area 6 No ignition sources No person carrying out work on a refrigerat...

Page 22: ... The check shall also take into account the effects of aging or continual vibration from sources such as compressors or fans 13 Detection of flammable refrigerants Under no circumstances shall potential sources of ignition be used in the search for or detection of refrigerant leaks A halide torch or any other detector using a naked flame may not be used 14 Leak detection methods The following leak...

Page 23: ...When transferring refrigerant into cylinders ensure that only appro priate refrigerant recovery cylinders are employed Ensure that the correct numbers of cylinders for holding the total system charge are available All cylinders to be used are designated for the recovered refrigerant and labelled for that refrigerant i e special cylinders for the recovery of refrigerant Cylinders shall be completed...

Page 24: ...Bosch Thermotechnology Ltd Cotswold Way Warndon Worcester WR4 9SW mailto Commercial enquiry uk bosch com Contact Number 03301233004 Web address www bosch industrial co uk ...

Reviews: