Conettix D6600/D6100IPv6/D6100i | Computer Interface Manual | 3.0 Computer Communication
Protocols
14
Bosch Security Systems, Inc. | 2012.09 | 4998122703-05
3.1.7
ADT SIA (Message Type S)
ADT SIA
Example
D6500 Byte Description
1
2
3
4
5
6
7
8
9
10 11 12 13 14 15 16 17 18 19 20 21
h
S
r
r
l
[
#
a
a
a
a
|
d
a
m m -
d
d
-
y
22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37 38 39 40 41 42
y
t
I
h
h
:
m m :
s
s
E
M M Z
Z
Z
Z
/
*** t
Table 9: ADT SIA (Message Type S) Byte Description
#
Title
Description
1
Header Character
(h)
Optional. Check with the computer automation software for
compatibility.
2
Message Type
S
3-4
Receiver Number Receiver gateway number from 01 to 99.
5
Line/Group
Number
Line number in the receiver gateway that sent the message.
6
space
One space.
7
#
#
8-11
Account Number
Up to sixteen digits in the account number.
12
|
Separator. Indicates more data positions after account number.
13-32
Date and Time
Date and time.
33
E
SIA block code.
34-35
Event Code
SIA event code (refer to
Appendix G: ADT SIA Report Codes
).
36-39
Zone
Zone number.
40
/
Separator.
41
***
Next block of data.
42
Trailer Character
Typically, this is HEX 14.