18 Ah batteries are required to meet 24‑hour standby requirements.
Minimum Standby UPS Power
The minimum UPS power required (in watts) = Total UPS Current (from the Calculating
Standby Current table) x 120 (voltage) x required hours of s 20% (storage).
Estimated BTU Load
The estimated BTU load for the system is calculated as follows: Total UPS Current (from the
Calculating Standby Current table) x AC voltage x 3.4 = Estimated BTU load