Graphic Keypads
Installer Reference Guide
7
Bosch Security Systems 03/16 Graphic Keypads BIRG FTR1.0
To have the keypad control a door on the system you
will need to assign the keypad to a door. See the Devic-
es-Keypads & Readers-Door Assignment menu option in
panel programming.
Once assigned with a door assignment, the on-board
Lock output and Egress input will automatically be as-
signed to the same door as the keypad.
If both alarm area and door control is required then
you will need to assign a home area and a door to the
keypad. In this case the LED indicators will display for
the area status and door status.
Keypad Alert Tones
Graphic keypads emit several distinct tones to alert you
to particular system events. The keypad volume level can
be adjusted if required. See Devices-Commands-Volume
menu in panel programming.
i
Note
Setting the keypad volume to off will also stop the
key press beep during normal operation.
Keypad Alert Tones
Event
Alert Tone Emitted
Fire
Alarm
If the system registers a fire alarm, the
reader will sound 3 short beeps fol-
lowed by a 1.5 second pause. This will
repeat until reset by the user or until
the siren run time expires.
Burglary
Alarm
If the system registers a burglary
alarm, the keypad will sound a con-
tinuous siren tone until reset by a user
or until the siren run time expires.
Trouble
If a system trouble condition occurs,
the keypad will sound 4 x fast short
beeps followed by a 5 second pause
and will repeat this tone until the user
acknowledges the trouble
condition from a display keypad
Key
Press
The keypad will sound one short beep
every time a button is pressed.
Exit
Delay
The exit delay warning will sound 1
short beep every second when the
area the keypad has been assigned to
is armed. During the last 10
seconds of exit time the warning tone
will speed up indicating that the time
has nearly expired.
Entry
Delay
The hi/lo entry delay warning tone will
sound once every second when an en-
try delay zone in the area the keypad
has been assigned to is triggered. If
the system is not disarmed before the
entry time expires then an alarm will
occur.
Error
If you press an invalid button during
any data entry sequence, the keypad
will sound a 2 second warning tone
indicating that the command was not
accepted.
Chime
Alert
If chime mode is active then the
keypad will sound fast short beeps
to alert the user when a zone pro-
grammed for chime is opened. Chime
mode is only applicable when the area
is disarmed.
Table 8: Keypad Tones
i
Note
Keypads alert tones can be disabled if required.
See the Devices-Keypads & Readers-Indicator Op-
tions menu in panel programming to disable these
features.
Egress and Lock Control
Smart Card enabled graphic keypads include an egress
input and a lock output which can be used to simplify
the wiring when the keypad is being used for door or
access control.
The lock output consists of a protected open collector
transistor that can be used to operate a relay to control
the door lock. The output will go from open to low for
fixed 5 seconds whenever the associated access group
or door assignment is triggered.
i
Note
The on board lock output will operate for a fixed
time period of 5 seconds when triggered. If a dif-
ferent time is required then you should use another
output on the system to operate the door lock.
The lock output, and LAN+ power supply are not de-
signed to operate and power the door lock directly. You
should always fit a relay and protection diode to the lock
output in combination with a separate power supply.
The optional CM444B Relay Module has been designed
to suit this task. If you require the door to operate when
the mains power has failed then you will also need to fit
a battery backup to the external power supply. See the
wiring diagram in Figure 9: for more details.
The Egress input allows you to simplify the wiring re-
quired to implement an egress button on the inside of