6 720 820 872 (2016/12)
CR 400 | CW 400 | CW 800
Installation | 11
The
outside temperature sensor
(included in the scope of
delivery of CW 400/CW 800/) is connected to the heat source.
▶ Observe the instructions for the heat source when
connecting the electrical supply.
When sensor leads are extended, apply the following lead
cross-sections:
•
Up to 20 m with 0.75 mm
2
to 1.50 mm
2
conductor cross-
section
•
20 m up to 100 m with 1.50 mm
2
conductor cross-
section.
3.5
Attaching or removing the user interface
Attaching the user interface
▶ Hook in the user interface at the top.
▶ Click in the user interface at the bottom.
Fig. 7
Attaching the user interface
Removing the user interface
▶ Press the button on the underside of the plinth.
▶ Pull the bottom of the user interface away from the plate.
▶ Remove the user interface by lifting upward.
Fig. 8
Removing the user interface
6 720 812 361-05.2O
1.
1.
2.
6 720 812 361-06.2O
3.
2.
1.