6 720 820 872 (2016/12)
CR 400 | CW 400 | CW 800
Commissioning | 21
Menu item
Question
Answer / setting
Start configuration wizard
Check before starting the configuration wizard:
•
Module installed and address set?
•
Remote control installed and set?
•
Temperature sensor installed?
Start the configuration wizard?
Yes
|
No
System data
Low loss hdr.
sensr. instll.
Is a low loss header installed? If yes, is a temperature
sensor installed? If yes, where is it electrically
connected?
No low-loss header
|
At the
boiler
|
At the module
|
Header w/
o sensor
Config. DHW at
boiler
How is DHW connected to the heat source (boiler)?
No DHW
|
3-way valve
|
Primary
pump
Config. of HC1 at
boiler
Is heating circuit 1 connected to the heat source
(boiler)? If yes, does it have a separate heating circuit
pump?
No heating circuit
|
No own
heating circuit pump
|
Own pump
Min. outdoor
temperature
With weather-compensated control: what is the
minimum outside temperature at the location on
average over the last few years?
– 35 ... 10 °C
Type of building
To what type of building is the heated building?
Light
|
Medium
|
Heavy
Boiler data
Pump type
Is the pump operated depending on the burner output
or the differential pressure?
Output-compensated
|
Delta P-
compensated 1...4
Pump run-on
time
How long must the pump run on after the shutdown of
the burner to discharge the heat from the heat source?
24h
|
1 ... 60 min
Heating circuit
1
Heating circuit
installed
Is heating circuit 1 installed? If yes, where is heating
circuit 1 electrically connected?
No
|
At the boiler
|
At the module
Ctrl type h. circ.
1
How should the temperature influenced by heating
circuit 1 be controlled?
Outdoor-temp.-compensated
|
Outside temp. with low end
|
Room-temp.-compensated
|
Room temperature output
|
Constant
User interface
What user interface is installed?
CR400
|
CW400
|
CW800
|
CR100
|
CR10
Heating system
heat circ. 1
What type of heating does heating circuit 1 operate?
Radiator
|
Convector heater
|
Underfloor
Set point
constant
If heating circuit 1 is configured as constant heating
circuit: To which temperature should the heating be
controlled?
30
...
85 °C
Max. flow
temperature
What is the maximum flow temperature that should be
set?
E.g.
30 ... 85 °C
Set heating
curve
Should the heating curve for heating circuit 1 be set?
(For further sub-settings
Æ
Chapter 7.1.3, from
page 32)
Æ
page 35, Tab. 16
Setback type
Which setback type should be used?
Reduced mode
|
Outside
temperature threshold
|
Room
temperature threshold
Table 9 Commissioning with the configuration wizard
Summary of Contents for CR 400
Page 63: ...6 720 820 872 2016 12 CR 400 CW 400 CW 800 63 Notes ...
Page 64: ......