Part III: Advanced Commands
FIRE TEST ? (C 5 + 8)
D1260 Owner’s Manual
© 2003 Bosch Security Systems
50410C
FIRE TEST ? (C 5 + 8)
Use this function to test fire points and other 24-hour points to be certain they function properly. You can review both
the tested and untested points at your command center to help pinpoint any problems.
Upon initiation, the fire test will test the fire bell pattern on the bell output and ring the command center fire bell for 2
seconds. The AC will be disabled for 4 minutes in order to test the system’s battery power. If the battery cannot maintain
the system for the 4-minute period, the command center will appear to go dead. If this happens, contact your security
company. At the end of the 4-minute period, AC is returned to the system and the panel restores. A message will be sent
to your security company upon initiation and completion of the Fire Test.
During the Fire Test, no 24-hour alarms will
be sent to your security company.
If there is no activity on the system for 20 minutes, the system will automatically exit from the Fire Test.
Using Fire Test
:
1.
Ensure your command center shows idle disarmed
text.
2.
Press the
COMMAND
key.
3.
The display shows
*System Command*
.
4.
Press the
5
key, followed by the
8
key.
+
Note:
If you prefer, you may use the Command Menu in place of steps 2 and 3 to initiate this function.
Press the Menu> soft key to enter the Command Menu,
then press Next> soft key repeatedly
until you reach the FIRE TEST ?> prompt then press the adjacent
soft key.
5.
When the display shows
### points remain to be tested
you can begin. (### is the number of points)
Test each point by first activating the detection device
to fault the point.
Note:
If you know the point number, you can enter it by pressing its number key and then the
ENTER key.
The display will change to show the point that was entered. If the point is invalid the message “Invalid Point” or
“This is not a valid walk point” appears.
6.
As you fault each point, your command center will
display the point text for 60 seconds and ring the fire
sounders for 2 seconds. This verifies that the detection
device is working properly. Your system automatically
resets smoke detectors.
Summary of Contents for D1260 Series
Page 2: ...D1260 Owner s Manual 50410C 2003 Bosch Security Systems ...
Page 4: ...Contents D1260 Owner s Manual 50410C 2003 Bosch Security Systems ...
Page 144: ...Appendix Passcode Worksheet D1260 Owner s Manual 50410C 2003 Bosch Security Systems Notes ...
Page 154: ...D1260 Owner s Manual 50410C 2003 Bosch Security Systems Notes ...