Figure 5.3: Transmitter and Receiver Placement
1 Receiver
4 EOL resistor
2 FACP
5 Minimum spacing = 1/10 x distance
3 Transmitter
6 Minimum spacing = 1/5 x distance
* maximum spacing between adjacent systems is 60 ft (16.3 m)
Notice!
When two or more adjacent detectors are installed in the same area, alternate the transmitter
and receiver locations. If the transmitter and receiver are not alternated, ensure the spacing
between the detectors is 1/5th the distance from the transmitter to the receiver.
Setup
Before performing a setup, ensure all connections are made and secure. Then, apply power to
the transmitter and receiver.
1.
To allow the transmitter to power up while the cover is off, press the transmitter’s Aim
Mode button located above the green LED as indicated in the following figure.
6
Long-range Beam Smoke Detectors
Notices | en
17
Bosch Security Systems, Inc.
Installation Instructions
2014.01 | 06 | F.01U.068.899