4
en | Notices
Long-range beam smoke detectors
2017.03 | 7.0 | F.01U.068.899
Installation manual
Bosch Security Systems, Inc.
1
Notices
Notice!
Before installing any fire alarm system, consult your local authority having jurisdiction (AHJ).
Before installing the module, become familiar with the Installation and Operation Guide for the
control panel you are using.
!
Caution!
In a power outage and restoral or an alarm reset, power is removed and reapplied to the
receiver. An internal setup procedure is initiated within the detector and can last for up to
2 minutes. During this period, the detector is not able to initiate signals. Avoid connecting
these detectors to circuits, such as those programmed for alarm verification, that remove and
reapply power.
1.1
Regulatory
FCC compliance
This equipment was tested and complies with the limits for a Class B digital device, pursuant
to Part 15 of the Federal Communications Commission (FCC) Rules. These limits are designed
to provide reasonable protection against harmful interference in a residential installation. This
equipment generates, uses, and can radiate radio frequency energy. When this equipment is
not installed and used according to the instructions, it might cause harmful interference to
radio communications. There is no guarantee that interference will not occur in a particular
installation.
If this equipment causes harmful interference to radio or television reception that can be
determined by turning the equipment off and on, correct the interference by:
–
Reorienting or relocating the receiving antenna.
–
Increasing the separation between the equipment and the receiver.
–
Connecting the equipment to an outlet on a circuit different from the circuit to which
receiver is connected.
–
Consulting the dealer or an experienced radio or TV technician for help.
Codes and standards
Install, test and maintain the module according to these instructions, NFPA codes, local codes,
and the authority having jurisdiction (AHJ). Failure to follow these instructions can result in
failure of a detector to initiate an alarm event. Bosch Security Systems, Inc. is not responsible
for improperly installed, tested or maintained devices.
1.2
Trademarks
All hardware/software product names used in this document are likely to be registered
trademarks and must be treated accordingly.
NFPA, NFPA 72, National Fire Protection Association, and National Fire Alarm and Signaling
Code are registered trademarks of the National Fire Alarm Association, Inc. in the United
States.