background image

D7050/D7050TH 

|

 

Installation Instructions | 6.0 

Programming 

 

Bosch Security Systems, Inc. | 9/06 | 47458E 

 

6.0 Programming 

Refer to the control panel’s reference guide for 
multiplex programming instructions. 

7.0 Testing 

Test the D7050/D7050THs immediately after 
installation. Also test these detectors according to the 
NFPA 72 or more often as required by local code. 

7.1 Operational 

Testing 

 

 

Notify all concerned parties before and 
after completing maintenance on or testing 
the 
fire alarm system. 

1.

 

Apply power to the system and check for alarms. 

a.

 

Note any detectors in alarm, as indicated by 
one or more flashes per second, and shut down 
the system if there are any alarms. 

b.

 

Remove the alarmed detectors and recheck for 
proper wiring. 

c.

 

If problems continue, replace the affected 
detectors or swap them with known good units 
to determine if the problem is caused by the 
detector. 

2.

 

When the system is free of alarms, check each 
detector to ensure the red LED indicator flashes 
approximately every 3 to 8 sec to confirm the 
detector properly operates. 

3.

 

Test each detector to ensure it causes a control 
panel alarm.  

4.

 

Alarm the detectors by doing one of the following: 
a.

 

To activate an internal reed switch, place a 
magnet horizontally against the detector’s side 
and centered over the “T” marked on the 
head.  

b.

 

Use a UL Listed aerosol smoke detector tester 
such as the Home Safeguard Industries’ 25S to 
simulate an alarm. Follow the instructions with 
the aerosol smoke detector tester. 

5.

 

When a detector alarms, the red LED indicator 
activates and flashes at least once per second. Clear 
the alarm by initiating a System Reset before 
proceeding to the next detector. 

7.2 Sensitivity 

 

Calibration is important in determining a 
detector’s continued operation. Depending 
on local regulations, calibration testing 
might be required more often than once a 
year. According to NFPA 72, perform a 
Calibration Test at installation and every 
other year thereafter. Perform a Functional 
Test monthly. 

Test the sensitivity to meet NFPA 72 requirements by 
conducting a Magnet Test (

Section 7.2.3 Magnet Test 

on 

page 6

)

, or by measuring the calibration voltage pins 

using a D1005 Test Cable (

Section 7.2.4 Voltage 

Measurement Test 

on page 6). Visually inspect the 

detector’s LED to quickly determine the calibration 
(

Section 7.2.2 Visual Check

). These tests confirm whether 

or not the detector is within its factory marked 
calibration range. 

7.2.1 Sensitivity 

Test 

The control panel continually monitors the 
D7050/D7050THs. If it exceeds the limits of the 
sensitivity thresholds, the control panel reports the 
detector in question and generates a fault condition. 

7.2.2 Visual 

Check 

The D7050/D7050TH includes the Chamber Check 
Automatic Trouble Indication that allows it to 
automatically show if its calibration is out of the factory 
listed range. This check meets the NFPA guidelines for 
sensitivity testing by visually inspecting the detector 
and checking the LED flash rate.   

If the calibration is out of range during power up or 
longer than 24 h, the Alarm LED begins double 
flashing. The LED flashes approximately once every  
3 to 8 sec when the detector operates normally. 

 

Visually check all detectors before 
disconnecting the multiplex bus. 
Disconnecting the bus erases the Chamber 
Check Automatic Trouble Indication. If the 
detector was disconnected or the control 
panel lost power within the last  
24 h, perform a Magnet Test or Voltage 
Measurement Test to confirm sensitivity. 

 

Summary of Contents for D7050

Page 1: ...EN Installation Instructions Multiplex Photoelectric Smoke Detectors D7050 D7050TH ...

Page 2: ...is device must accept any interference received including interference that might cause undesirable operation 1 0 Description The D7050 D7050TH are Underwriters Laboratories Inc UL Listed open area multiplex photoelectric smoke detectors The D7050TH includes a built in 135 F 5 F 57 C 2 7 C heat detector Both detectors can be used with the D7024 or DS9400M FACP containing a D7039 or DS9431 Module E...

Page 3: ...ide P N 38685 or the DS9431 Installation Instructions P N 41381 Do not exceed a maximum line resistance of 50 Ω 3 0 Wiring the D7050 B6 Base You can wire the D7050 B6 Base in series or T tap refer to Figure 2 Figure 2 Wiring the D7050 B6 Base 1 R2 3 1 R2 3 1 2 3 1 1 R2 3 1 R2 3 1 R2 3 1 R2 3 1 R2 3 1 R2 3 1 Input output module for the D7039 or DS9431 2 Series connection 3 T tap connection You can ...

Page 4: ... P N 44578 for additional address limitations The A address range works on the D7039 Multiplex Expansion Module with the D7024 FACP The B address range works on the DS9431 Multiplex Expansion Module with the DS9400M FACP Figure 3 shows the A address range set at 095 allowing the D7039 to work with the D7024 FACP 5 0 Mounting 1 Unscrew the tamper screw located in the recess on top of the dust cover...

Page 5: ...proceeding to the next detector 7 2 Sensitivity Calibration is important in determining a detector s continued operation Depending on local regulations calibration testing might be required more often than once a year According to NFPA 72 perform a Calibration Test at installation and every other year thereafter Perform a Functional Test monthly Test the sensitivity to meet NFPA 72 requirements by...

Page 6: ...e D7050 4 Multiply the voltage by two The result should be within the factory marked calibration range printed on the label on the bottom of the detector 5 If the detector is outside the factory marked calibration range remove and clean it or replace it as described in Section 7 1 Operational Testing beginning on page 5 6 Recheck the calibration voltage measurement If the detector is still outside...

Page 7: ...lel to the chamber and gently snap the locking tabs into place 7 Replace the detector cover and carefully align the LED and thermistor holes 8 Return the detector to its base 9 Test the detectors for proper calibration using one of the tests described in Section 7 0 Testing beginning on page 5 Do not paint the D7050 D750THs Paint or other foreign matter covering the screens can stop or delay smoke...

Page 8: ... 2006 Bosch Security Systems Inc 47458E Bosch Security Systems Inc 130 Perinton Parkway Fairport NY 14450 9199 Customer Service 800 289 0096 Technical Support 888 886 6189 ...

Reviews: