Commissioning
5–11
1070 066 028-101 (01.05) GB
P15 (A-0-0015)
Adjustment f = f
max
(Adjustment to maximum setpoint)
Setpoint input X 23.5/6 can be adjusted in the range of
$
5...
$
13 V,
setpoint input X 23.5/7 can be adjusted in the range of 10...27 mA.
It is also possible to set a unipolar setpoint range:
e.g., 0 ... +10 V with
f = f
max
adjustment to +10 V
f = 0
adjustment to +5 V
The f=f
max
adjustment and the f=0 adjustment can be made in any order.
factory adjustment to
$
10 V
all
DMs, DS
Eu0
(0)
Eu1
(1)
normal display
short-time during
f
max
adjustment
automatic
return
Procedure:
D
Switch line voltage on.
D
Do not activate enable signal !
D
Enter the analog value of the maximum output frequency at the set-
point connector.
D
Select P15.
D
Select ’Eu1’ using the
or
keys. When adjustment is done, the
display returns to ’Eu0’.
D
Store the f
max
adjustment by depressing the ’D’ key. Another adjustment
may be carried out.
P16 (A-0-0016)
f = 0 adjustment (offset adjustment)
all
DMs, DS
Eo0
(0)
Eo1
(1)
normal display
short-time during
f=0 adjustment
automatic
return
Procedure:
D
Switch line voltage on.
D
Do not activate enable signal !
D
Enter the analog value for the output frequency of 0 Hz at the setpoint
connector.
D
Select P16.
D
Select ’Eo1’ using the
or
keys. When adjustment is done, the
display returns to ’Eo0’.
D
Store the f=0 adjustment by depressing the ’D’ key. Another adjustment
may be carried out.