Commissioning
5–15
1070 066 028-101 (01.05) GB
P22 (A-0-0022)
Braking current
The amount of the braking force or the holding torque at zero speed is
determined by the braking current. If the braking current is higher, the motor
heats up faster.
Typical setting range:
x
rated motor current.
min.
Range
[A]
max.
DM 4K
0.9
0.1
6.7 A
DM 8K
0.9
0.1
6.7 A
DM/DS 15K
1.5
0.5
11.2 A
DM 30K/A
3.1
0.5
22.5 A
DM/DS 45K/A
4.7
0.5
33.8 A
DM 85B
9.5
0.5
67.7 A
DM140D
12.7
0.5
90.3 A
factory setting
P23 (A-0-0023)
Braking/stopping time
The braking/stopping time refers to DC braking when the enable signal has
been deactivated (see page 5–14).
0.1
999 sec
smallest step
Range [sec]
factory
setting
all
DMs, DS
0.1
1
100
min.
max.
P24 (A-0-0024)
Direct current brake starting frequency (f
start
)
The direct current brake is activated if f
act
< f
start
, depending on P21.
0.0
999 Hz
smallest step
Range [Hz]
factory
setting
all
DMs, DS
0.1
1
100
min.
max.