4
C. Level and Position Range
- Level range by adjusting the
(4) leveling legs with a wrench. Note: A minimum clearance
of 1/8" is required between the bottom of the range and the
leveling leg to allow room for the bracket. Use a spirit level
to check your adjustments. Slide range back into position.
Visually check that rear leveling leg is inserted into and
fully secured by the Anti-Tip Bracket by removing lower
panel or storage drawer. For models with a warmer drawer
or broiler compartment, grasp the top rear edge of the
range and carefully attempt to tilt it forward.
2. Provide an adequate gas supply.
This unit is pre-set to operate on 4" natural gas manifold
pressure. A convertible pressure regulator is connected to the
manifold and MUST be connected in series with the gas supply
line. If the LP/Propane conversion kit has been used, follow
instructions provided with the kit for converting the pressure
regulator to LP/Propane use. The LP kit can be found on the
back side of the range (some models).
Care must be taken during installation of range not to obstruct
the flow of combustion and ventilation air.
For proper operation
, the maximum inlet pressure to the
regulator should be no more than 14 inches of water column
pressure. The inlet pressure to the regulator must be at least
1 inch greater than regulator manifold pressure. Examples: If
regulator is set for natural gas 4 inch manifold pressure, inlet
pressure must be at least 5 inches; if regulator has been
converted for LP/Propane gas 10 inch manifold pressure, inlet
pressure must be at least 11 inches.
Leak testing of the appliance shall be conducted according to
the instructions in step 4g.
The gas supply line should be 1/2" or 3/4" I.D.
3. Seal wall openings.
Seal any openings in the wall behind the range and in the floor
under the range after gas supply line is installed.
30" GAS RANGE INSTALLATION INSTRUCTIONS
(For Models with Sealed Top Burners)
Fig. 4a
Fig. 4b
Fig. 4c
Wall
Edge
23"
15"
2"
7"
11-1/2"
10-1/2"
Recommended area for
120V outlet on rear of
wall and area for thru
the wall connection of
pipe stub and shut-off
valve is shaded area.
Recommended area for thru
the floor connection of
pipe stub and shut-off valve.
Centerline
of range
Centerline
of range
CL
4.
Connect the range to the gas supply.
NOTE: To prevent leaks use pipe joint sealant on all male
(outside) pipe threads.
*Please note:
Models without
self-cleaning
feature may
have an
additional 4 to
7 inches
clearance from
the floor.
*