20
en | Accessories
Conventional Automatic Detectors
F.01U.002.707 | 8.0 | 2011.10
Operation Guide
Bosch Sicherheitssysteme GmbH
Three inputs (terminal 2 to terminal 4) allow the adaptation to the different line technologies.
Connection on reliance to the used line technology
Line Technology
Fire Panel
Terminals Used
Conventional
BZ 1060
1 + 2
Conventional
FPA-5000, UEZ 1000, UGM 2020, FP 102/104/106
1 + 3
LSN
FPA-5000, BZ 500 LSN, UEZ 1000, UEZ 2000 LSN,
UGM 2020
1 + 4
Terminal
Connector
1
Ground
2
Input flashing (LED flashes)
3
Input static (LED steady on)
4
Input static (LED steady on)
Connect onto terminal 4 only via pre resistor, otherwise the LED could
be destroyed.
All current Bosch fire detectors are equipped with an internal resistor
to restrict current consumption.
1 2 3 4
CAUTION!
If the current consumption for the connected detector exceeds 20 mA, it can lead to the
malfunction of or damage to the MPA External Detector Alarm Display. You should restrict the
maximum detector current consumption to 20 mA to avoid damaging the FAA-420-RI.
NOTICE!
The cable length between the detector and the MPA must not exceed 3 m when connected by
an unscreened cable.
Technical Specifications MPA
Operating voltage
9 V DC to 30 V DC
Maximum current consumption
–
Terminal 2
–
Terminal 3
–
Terminal 4
–
approx. 2 mA
–
limited to 13 mA
–
limit to maximum 20 mA
Display medium
1 LED
Permissable wire gauge
0.6 mm to 0.8 mm
Dimensions
79 x 79 x 31 mm
Weight
approx. 65 g
VdS approval number
G 294 052