48
en | Planning
FCS-320-TM Aspirating Smoke Detector
F.01U.130.928 | 1.0 | 2009.11
Operation Guide
Bosch Sicherheitssysteme GmbH
3.8.2
U-Pipe System - Simplified Planning
3.8.3
M-pipe system - simplified planning
1 pipe system
FCS-320-TM
FCS-320-TM-R
Figure 3.12
U-pipe system, e.g. for equipment protection
Limiting values
Min. distance FCS-320-TM – T-fitting
2 m
Max. distance FCS-320-TM – T-fitting
20 m
Max. branch length
25 m
Max. total pipe length per pipe system
–
Pipe Ø 25 mm
–
Additional pipe Ø 12 mm
50 m
8 x 3 m
Max. total pipe length per pipe system for a fan voltage < 10.5 V
–
Pipe Ø 25 mm
–
Additional pipe Ø 12 mm
40 m
8 x 3 m
Max. number of air sampling openings (n) per pipe system
8 units
Min. distance between 2 air sampling openings
0.1 m
Max. distance between 2 air sampling openings
4 m
U-pipe system
Number of air sampling openings
2
4
6
8
Ø of all air sampling openings in mm
a
6.0
4.2
3.4
3.0
a
Punch diameter of the aspiration reducing film sheet
E
D
C
B
A
10
9
8
7
6
5
4
3
2
1
FAS-420-TM
series
FAS / FCS
1 pipe system
FCS-320-TM
FCS-320-TM-R
Figure 3.13
U-pipe system, e.g. for equipment protection
d
FAS / FCS