FCS-320-TM Aspirating Smoke Detector
Planning | en
51
Bosch Sicherheitssysteme GmbH
Operation Guide
F.01U.130.928 | 1.0 | 2009.11
When installing a pipe system in air-conditioning ducts, the following must be observed:
–
Since the FCS-320-TM and the pipe system are located in different pressure ranges, an
air return pipe (see
Figure 3.18
) must be provided.
–
The pipe entries into the duct must be airtight.
–
The portion of the pipe system that is outside the duct must be sealed airtight.
Figure 3.16
Direction change of the duct without air baffles
1
Main speed range
2
Exceptional arrangement of the
pipe system (if distance of
3 x d
min
cannot be observed)
3
Typical pipe system
arrangement
d
min
Smallest duct diameter
Figure 3.17
Sound dampers in a duct
1
Smoke aspiration pipe
2
Air-conditioning duct
3
Main speed range
4
Sound dampers
5
Bore
3 x d
min
1
2
3
1
2
3
4
5