FCS-320-TM Aspirating Smoke Detector
Commissioning | en
79
Bosch Sicherheitssysteme GmbH
Operation Guide
F.01U.130.928 | 1.0 | 2009.11
6.4
Checking the Detection Unit and Alarm Transfer
1.
Trigger the FCS-320-TM using test aerosol. Spray the test aerosol either into the first air
sampling opening or into the test adapter on the pipe system.
2.
Use the table below to check the transmission line to the fire panel.
6.5
Checking malfunction transmission
Check…
If this is not the case, ...
–
Whether the alarm is displayed on the
aspirating smoke detector
–
Check whether the display board is
connected
–
There is a fault with the aspirating smoke
detector Replace the detection unit
–
Whether the alarm is transmitted to the
fire panel and reported on the
appropriate line
–
Check the transmission lines
NOTICE!
Note all checked data in the test log.
NOTICE!
The steps below may only be carried out following an airflow calibration in accordance with
Section 6.3 Calibrating the Airflow Sensor
.