FCS-320-TM Aspirating Smoke Detector
Commissioning | en
83
Bosch Sicherheitssysteme GmbH
Operation Guide
F.01U.130.928 | 1.0 | 2009.11
2.
Free up the 4.6 mm and 4.2 mm aspiration borings on the test pipe again.
3.
In the "Settings" screen, click on the [Set] button at the bottom and start the airflow
initialization by pressing the [Initialising] button.
The fault messages and indications must go out. The "Active Initialisation" field in the
"Settings" screen of the diagnostic software flashes while initialization is in progress.
NOTICE!
Once the aspiration borings have been closed, the device reports the malfunctions "Air flow
too low (static evaluation)" and "Detector module fault" within 30 seconds.