6.2. Arrangement of the detectors in a tilted roof
max. 7m
max. 14 m
max. 7 m
α
max. 14 m
D
L
D
L
D
L
min. 0.5 m
Depending on the roof pitch
α
and the room height R
H
,
the detector and the reflectors must be arranged such that the
light beam in distance D
L
runs below the ceiling.
min. 0.5 m
6.3. Arrangement of the detectors in a saddleback roof
α
max. 7m
max. 14 m
max. 7 m
min. 0.5 m
max. 14 m
min. 0.5 m
D
L
D
L
D
L
Depending on the roof pitch
α
and the room height R
H
, the detector
and the reflectors must be arranged
such that light beam in distance D
L
runs below the ceiling.
Depending on local rules and regulations, different distances may be
prescribed or permissible if necessary.